Controller.AccountManagementGuidelines

The Account Management Guidelines of the controller are described below. The focus here is on Controller.UserManagement, Controller.WebDiagnosis, Controller.ProcessVisualization and the SSH / SFTP access.

 

Controller.AccountManagementGuidelines :: Controller.UserManagement

Default / Factory Settings:

The User Management of the Controller is activated and must be used the first time via the PLC Designer. During this routine the user has to change the password:

  • Administrator (user) | "Administrator" (group) | "Admin123" (password)
    <password> has to change during first use.

  • "Anonymous_OPCUAServer" (user) | "Anonymous_OPCUAServer" (group) |"" (password)
    The empty string password is not relevant, as this user is intended exclusively for anonymous use of the OPC UA server, and it is precisely this anonymous use that does not require a password.

Account Handling:

  • New users and groups can be defined using the PLC Designer.

Policies:

The Runtime Password Policy is deactivated by default. It is recommended to activate it and adapt it to the current password strength requirements. Current default settings after activation are:

  • Minimum length = 8

  • Number of unique characters = 4

  • Requires lowercase letter = activated

  • Requires uppercase letter = activated

  • Requires digit = activated

  • Requires special character = activated

  • Must not contain username = activated

 

Controller.AccountManagementGuidelines :: Controller.WebDiagnosis

Default / Factory Settings:

  • "guest" (user) | "guest" (group) | "guest" (password)
    After logging in for the first time, a new password must be assigned.

  • "advanced" (user) | "advanced" (group) | "default" (password)
    After logging in for the first time, a new password must be assigned.

Account Handling:

  • After logging in for the first time, new passwords for the "guest" and the "advanced" user must be assigned.

  • After a successful login, each user can change their own password.

Policies:

  • Minimum length = 4 characters

 

Controller.AccountManagementGuidelines :: Controller.ProcessVisualization

Default / Factory Settings:

The controller is delivered without process visualization. This must be created and installed by the customer using the UI Designer.

Account Handling:

User management for the process visualization must be activated when creating the process visualisation with the UI Designer. The following settings can be selected.

  • It is possible to create four user roles for "Administrators", "Operators", "Service technicians" and "Managers".

  • It is possible to activate an auto-logon for test purposes. A message appears stating that the login page will no longer appear. It is only recommended to use this auto-logon for test purposes and not in a productive plant.

  • It is possible to create a guest account. If activated, the "guest" (user) is prompted with the "guest" (password), which can be changed immediately by the customer.It is recommended that you change the default password.

Policies:

The policy can be specified. The following values are stored by default:

  • Minimum Password Length = 4

  • Maximum password length = deactivated

  • Allow password reuse after <> days = deactivated

  • Allow password reuse after <> Password changes = deactivated

  • Minimum difference = deactivated

  • Maximum subsequent equal characters = deactivated

  • Minimum difference to prior password <> characters = deactivated

  • Password must contain letters = deactivated

  • Password must contain digits = deactivated

  • Password must contain special characters = deactivated

  • Password must contain lowercase and uppercase letters = deactivated

  • Password must not be equal to user name = deactivated

 

Controller.AccountManagementGuidelines :: SFTP

Default / Factory Settings:

By default, no customer keys are present in the delivery state.

Key Handling:

  • The customer can store their own customer key.

Policies:

The customer.pkk customer key has the following requirements:

  • RSA