L_IOSP - BaseEventType

For the execution of Methods via OPC UA corresponding objects must be existing in the OPC UA information model as well as in the PLC application. In addition to this, both entities must then be mapped. This can be done with the Lenze Mapping Editor.

This generic function block L_IOSP_BaseEventType represents an OPC UA BaseEventType in the IEC application, which can be mapped to an BaseEventType in the OPC UA Nodeset.

This basic function block contains all the variables necessary for the mapping of the event to the OPC UA Server. In addition to this, it provides a few sub-methods for the event operation in the PLC application.

 

 

 

L_IOSP_BaseEventType

 

 

 

BOOL

–

 

xExecute

xDone

 

–

BOOL

BOOL

–

 

xEventTriggered

xBusy

 

–

BOOL

 

 

 

 

xTriggerEvent

 

–

BOOL

 

 

 

 

EventID

 

–

L_IOSP_ByteString

 

 

 

 

Message

 

–

L_IOSP_LocalizedText

 

 

 

 

Severity

 

–

USINT

 

 

 

 

SourceName

 

–

String

 

 

 

 

SourceNode

 

–

L_IOSP_NodeID

Inputs

Name

Data type

Information/possible settings

xExecute

BOOL

FALSEäTRUE

Executes the event operation.

xEventTriggered

BOOL

FALSEäTRUE

The event has been fired by the Server.

If the function block is mapped, this variable is internally connected to the OPC UA Server.

Outputs

Name

Data type

Value/meaning

xDone

BOOL

If TRUE, signals the PLC application that the event is sent by the OPC UA Server.

xBusy

BOOL

If TRUE, signals the PLC application that the event operation is in progress.

xTriggerEvent

BOOL

If TRUE,Signals the OPC UA Server that the event shall be fired.

If the function block is mapped, this variable is internally connected to the OPC UA Server.

EventID

L_IOSP_ByteString

OPC UA specific value.1) Shall be generated by the Server application to uniquely identify a particular Event Notification.

 

Message

L_IOSP_LocalizedText

OPC UA specific value.1) Shall provide a human-readable and localizable text description of the Event. If not set the BrowseName will be used.

 

Severity

USINT L_IE1P_Error

OPC UA specific value.1) It is an indication of the urgency of the Event. Values will range from 1 to 1 000, with 1 being the lowest severity and 1 000 being the highest.

Here you can find information on error or warning messages.

SourceName

String

OPC UA specific value.1) SourceName provides a description of the source of the Event. If the Event is not specific to a source the SourceName can be empty.

SourceNode

L_IOSP_NodeID

OPC UA specific value.1) The SourceNode Property identifies the Node that the Event originated from. If the Event is not specific to a Node the SourceNode can be empty.

1)

For more information, see:

OPC 10000-5 Unified Architecture Part 5 Information Model Base Event Type | OPC UA Online Reference (opcfoundation.org)

Sub-Methods

This function block provides following methods for the method operation in the PLC application.

Name

Description

StartEvent()

 

This method is called automatically once, if the OPC UA Event is executed by the PLC application (xExecute FALSEäTRUE).

It is used to prepare the event operation, e. g. to determine the EventId, to initialize additional function blocks or to prepare a consistent data input set.

This method is optional.

ExecuteEvent()

Output variable:

xComplete

BOOL

This method is called automatically cyclically, after the StartEvent() call.

It is used to provide the event properties, e. g. getting device parameter via an additional function block for an application specific property.

The cyclic call of this method is terminated if xComplete is set to TRUE by the application. The OPC UA Server is triggered to send the event.

ResetEvent()

 

This method is called automatically once, after the ExecuteEvent () calls and the OPC UA Server signals, that the event is sent.

It is used to reset the event operation, e. g. to reset additional output variables.

This method is optional.

The OPC UA Client Server connection is a none realtime communication. Thus, the PLC application is not synchronized with the communication. In order not to disturb the PLC realtime task, the Server FB L_IOSP_BaseEventType should be executed in a low prio task without watchdog or free-wheeling task.