The PROFIsafe parameters of an F-Device are located in the editor of the logical I/Os of the F-Device:
-
Tab: Safe parameterization: i-parameters. These are the safety-oriented device parameters from PROFIsafe devices.
-
Tab: Safe Configuration: F-Parameters. These are the protocol parameters of PROFIsafe.
The variables that are used for the safety application to access the I/Os are defined on the I/O Mapping tab of the editor.
For a more detailed description of the editor and its tabs, refer to Device Editor of Logical I/Os.
Which of the F-Parameters listed below are actually used depends on the device.
-
F_Check_SeqNr-
V2 mode: A sequential number that is always to be included in the CRC2 generation
-
Not editable
-
-
F_Check_iPar-
Manufacturer-specific use within a homogeneous system
-
Not editable
-
-
F_SIL-
SIL which the user requires from the respective F-Device. It is compared with the manufacturer's specification.
-
Editable
-
-
F_CRC_Length-
CRC length
-
Value: 3-byte CRC
-
-
F_Par_Version-
Version number of F-Parameters/FSCT 3/1 operating mode
-
Preset value: V2 mode (only V2 is supported)
-
Editable
-
-
F_Block_ID-
Identification of the type of parameter block
-
Not editable
-
-
F_Source_Add-
Editable
-
F_Par_CRCchanges when there is a change toF_Source_Add.
-
|
Caution |
|---|---|
|
The user must ensure that the F-Host has a unique source address within the PROFINET network and PROFIBUS fieldbuses (even for several safety controllers in the same fieldbus). For topology T2 when several safety controllers are below the same PROFIBUS/PROFINET master: The uniqueness of |
|
Tip |
|---|---|
|
The user must ensure through organizational means that the |
-
F_Dest_Add-
Unique target address of the F-Device in the PROFIsafe network.
-
If several F-Hosts are used for controlling a plant, it is recommended to give to all F-Devices a unique
F_Dest_Add. To this end, it is recommended that the user makes a list with the ranges of values forF_Dest_Addthat are permissible for the individual hosts.
This must also be realized even in the case of failure to satisfy the prerequisite that each F-Device is connected to precisely one F-Host via the wiring and thus receives its F-Parameters only from this F-Host.
-
-
Editable
-
F_Par_CRCchanges when there is a change toF_Dest_Add.
-
|
Caution |
|---|---|
|
The user must ensure that all F-Devices have a unique destination address |
|
Tip |
|---|---|
|
The user must make sure that the |
-
F_WD_Time-
Time specification (in milliseconds) for the watchdog timer that monitors the duration until the receipt of the next valid PROFIsafe message.
-
Default value of the GSD file: Maximum processing time of the F-Device
-
Editable
-
F_Par_CRCchanges when there is a change toF_WD_Time.
-
-
F_iPar_CRC-
CRC that is calculated from the i-Parameters of the F-Device.
-
F_Par_CRCchanges when there is a change toF_iPar_CRC.
-
|
Tip |
|---|---|
|
As the value of F_iPar_CRC, the value of the CRC must be entered manually by means of the i-Parameters of the F-Device. The CRC for the i-Parameters is located on the Safe parametrization tab of the logical I/O of the F-Device or in the respective F-Device manufacturer-specific tool. |
-
F_Par_CRC-
CRC for all F-Parameters
-
Calculation by safe editors
-
This ensures the error-free transmission of the F-Parameters.
-
Not editable
-