Environmental conditions

Ambient conditions
Climatic
Storage/transport
EN 60721-3-2
2K3: -25 ... +60 °C
Operation
EN 60721-3-2
3K3:
c520: 0°C to 60°C for horizontal installation
c550 (with fan): 0°C to 60°C for horizontal installation
Note:
The buffer time of the RTC is designed for four weeks. Depending on the ambient temperature, the buffer time may be derated.
Air humidity
EN 60721-3-3
2K3 (without condensation, relative humidity 10 ... 95 %)
Pollution
EN 61010-1
Pollution degree 2
Mechanical
Shock/vibration
IEC 61131-2:2007 (sine, shock)
EN 60721-3-3 3M5
Vibration in accordance with IEC 60068-2-6, test Fc:
–
5 Hz - 8.4 Hz - deflection 3.5mm
 
–
8.4 Hz - 200 Hz 1 g acceleration
 
–
Rate of change 1 octave/min
 
–
10 frequency cycles per axis (also covers the test in compliance with EN 60721-3-3 class 3M5)
 
Shock complying with the specifications of IEC 60068-2-27
–
Test Ea: half-sine
 
–
15 g
 
–
11 ms
 
–
Half-sine
 
–
25 g
 
–
6 ms duration
 
–
3 shocks per axis for each direction (a total of 18 shocks)
 
–
2 Hz - 13.2 Hz - deflection +/-1mm
 
–
13.2 Hz - 100 Hz 0.7 g acceleration
 
–
Rate of change 1 octave/min, runtime depending on the resonance point determination
 
Site altitude
Storage/transport
< 12000 m amsl
Operation
< 3000 m amsl