The output shafts make a cracking sound

For motion applications in drive technology, a defective synchronization of 2 shafts leads to an audible clicking noise.
Cause
The task and DC cycle times set in the logic/motion system differ.
Error message
-
Remedies
Adjust the task cycle time and DC cycle time.
 
Cause
Wiring error: The EtherCAT terminals (IN/OUT) of the slave were inverted. A fieldbus scan does not indicate this error!
Error message
EtherCAT_Master: Set master 'Operational' failed. DCM not in-sync
Remedies
Correct wiring. Afterwards, reload the »PLC Designer« application into the automation system.
 
Cause
Clicking noise of the shafts after "out-of-sync"
If due to a fault, the preset DC deviation limit is exceeded, a re-synchronization of the DC slaves is carried out until the slaves are synchronized again ("In-Sync") and the DC deviation is under the preset limit value again.
Currently, the Lenze controller is not re-synchronized to the distributed clocks, such that the sync pulses of the master and the ones of the slaves are different.
Error message
EtherCAT_Master: DC slaves 'out-of-sync'. Deviation xxxxxxxx ns
Remedies
Restart the EtherCAT fieldbus so that the DC slaves and the DC master synchronize again.
 
Cause
Wrong selection of the device sync source. After the sync source has been changed, the subsequent download and the setting of the slave to the Operational state may fail.
Error message
-
Remedies
–
Manual setting of the code
 
–
Repeated download with PLC start
 
–
Restart the EtherCAT fieldbus by resetting the SoftMotion drive