Parameter data transfer
The EtherCAT device possesses two categories of parameters:
–
Standard communication parameters (index range 0x1000 ... 0x1FFF and 0xF050, Detected Module List).
These parameters are only visible/accessible for the EtherCAT masters connected via this interface.
The controller itself is unable to access the standard communication parameters.
These parameters are only visible/accessible for the EtherCAT masters connected via this interface.
The controller itself is unable to access the standard communication parameters.
–
For diagnostic parameters, see EtherCAT device diagnostics
Standard communication parameters
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x1000
|
Device type
|
RO
|
|
|
0x1001
|
Error register
|
RO
|
|
|
0x1008
|
Manufacturer's device name
|
RO
|
|
|
0x1009
|
Manufacturer's hardware version
|
RO
|
|
|
0x100A
|
Manufacturer's software version
|
RO
|
|
|
0x1018
|
Identity object
|
RO
|
|
|
0x1630
0x164F
|
RxPDO mapping
|
RW
|
|
|
0x1A30
0x1A4F
|
TxPDO mapping
|
RW
|
|
|
0x1C00
|
Sync manager type
|
RO
|
|
|
0x1C12
|
SM2 PDO assignment
|
RW
|
|
|
0x1C13
|
SM3 PDO assignment
|
RW
|
|
Tab. 1: Standard communication parameters (via EtherCAT interface)
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0xF050
|
Detected module list
|
RO/ARRAY OF UDINT
Array with objects of type "UDINT" which contains the currently configured/detected modules. Can be used for a device scan for reading the current configuration.
SubIndex 0 (USINT) contains the currently configured/detected number of modules.
|
|
Tab. 2: Detected module list (via EtherCAT interface)