Saving the settings

Parameter
Address
Name / setting range / [default setting]
Information
0x2829
(P732.00)
Automatic storage in the memory module
(Auto-Save EPM)
1 = Activate automatic saving of parameters in the memory module. Saving is undertaken to a parameter stored on the memory module with each write cycle. An excessively high number of write cycles reduces the service life of the memory module.
–
With the setting 0, the "Save user data" 0x2022:003 (P700.03) device command must be explicitly executed, or the enter key must be pressed and held for longer than 3 s to save the current parameter settings in the memory module of the inverter with mains failure protection.
 
Warning
The "Automatic saving" function must not be used together with cyclical writing of parameters via PDO.
0
Inhibit
1
Enable