Configure status display - Custom units

During operation, the keypad displays the output frequency of the inverter, or with an active PID control it shows the process controller setpoint. Alternatively, an optional diagnostic parameter can be displayed during operation.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2864
(P703.00)
Keypad status display
(KP status displ.)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
0 = normal display depending on the operating mode
–
In case of an active frequency control, the keypad displays the output frequency of the inverter.
 
–
In case of active PID control, the keypad displays the current Process controller setpoint in [P-Unit].
 
As an alternative, an optional diagnostic parameter can be set here, which is to be shown on the keypad during operation.
–
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
 
–
The lowest byte is always 0x00.
 
–
The keypad can be used to select the desired diagnostics parameter from a list.
 
0x2865:001
(P709.01)
Keypad display setup: User unit MS velocity mode
(KP disp. setup: User MS velocity)
Optional setting of an individual unit for the keypad operation display of the output frequency.
–
Setting is only possible with »EASY Starter«.
 
–
Maximum text length = 6 ASCII characters.
 
0x2865:002
(P709.02)
Keypad display setup: User unit PID control
(KP disp. setup: User PID control)
Optional setting of an individual unit for the keypad operation display of the current process controller setpoint.
–
Setting is only possible with »EASY Starter«.
 
–
Maximum text length = 6 ASCII characters.
 
0x4002
(P702.00)
Speed display scaling
(Scal.speed fact.)
0.00 ... [0.00] ... 650.00
Factor for the scaling of the speed display in 0x400D (P101.00).
–
With the setting "0.00", no scaling takes place.
 
–
Example: with the "16.50" and the actual frequency = 50 Hz, 0x400D (P101.00) shows the speed "825 units".