Favorites parameter list (default setting)

In the default setting, parameters for resolving typical applications are defined as "Favorites”.
 
No.
Display code
Name
Default setting
Setting range
Information
1
P100.00
Inv. outp. freq.
x.x Hz
- (Read only)
2
P103.00
Actual current
x.x %
- (Read only)
3
P106.00
Motor voltage
x VAC
- (Read only)
4
P150.00
Error code
-
- (Read only)
5
P200.00
Control select.
Flexible I/O [0]
Selection list
6
P201.01
Freq. setp. src.
Analog input 1 [2]
Selection list
7
P203.01
Start method
Normal [0]
Selection list
8
P203.03
Stop method
Standard ramp [1]
Selection list
9
P208.01
Mains voltage
230 Veff [0]
Selection list
10
P210.00
Min. frequency
0.0 Hz
0.0 ... 599.0 Hz
11
P211.00
Max. frequency
50.0 Hz* | 60.0 Hz**
0.0 ... 599.0 Hz
12
P220.00
Accelerat.time 1
5.0 s
0.0 ... 3600.0 s
13
P221.00
Decelerat.time 1
5.0 s
0.0 ... 3600.0 s
14
P300.00
Motor ctrl mode
VFC open loop [6]
Selection list
15
P302.00
V/f charac.shape
Linear [0]
Selection list
16
P303.01
Base voltage
type-dependent
0 ... 5000 V
17
P303.02
Base frequency
type-dependent
0 ... 1500 Hz
18
P304.00
Limit. rotation
Both rot. direct [1]
Selection list
19
P305.00
Switching freq.
type-dependent
1 ... 33
20
P306.01
Duty selection
Heavy Duty [0]
Selection list
21
P308.01
Max.load.for 60s
150 %
30 ... 200 %
22
P316.01
Fixed V/f boost
type-dependent
0.0 ... 20.0 %
23
P323.00
Rated mot.curr.
type-dependent
0.001 ... 500.000 A
24
P324.00
Max. current
200.0 %
0.0 ... 3000.0 %
25
P400.01
Enable inverter
TRUE [1]
26
P400.02
Run
Digital input 1 [11]
27
P400.03
Quick stop
Not connected [0]
28
P400.04
Reset fault
Digital input 2 [12]
29
P400.05
DC braking
Not connected [0]
30
P400.06
Start forward
Not connected [0]
31
P400.07
Start reverse
Not connected [0]
32
P400.08
Run forward
Not connected [0]
33
P400.09
Run reverse
Not connected [0]
34
P400.13
Reverse rot.dir.
Digital input 3 [13]
35
P400.18
Setp: Preset b0
Digital input 4 [14]
36
P400.19
Setp: Preset b1
Digital input 5 [15]
37
P400.20
Setp: Preset b2
Not connected [0]
38
P420.01
Relay function
Rdy for operat. [51]
Selection list
39
P420.02
DO1 function
Release brake [115]
Selection list
40
P430.01
AI1 input range
0 ... 10 VDC [0]
Selection list
41
P430.02
AI1 freq @ min
0.0 Hz
-1000.0 ... 1000.0 Hz
42
P430.03
AI1 freq @ max
50.0 Hz* | 60.0 Hz**
-1000.0 ... 1000.0 Hz
43
P440.01
AO1 outp. range
0 ... 10 VDC [1]
Selection list
44
P440.02
AO1 function
Outp. frequency [1]
Selection list
45
P440.03
AO1 min. signal
0
-2147483648 ... 2147483647
46
P440.04
AO1 max. signal
1000
-2147483648 ... 2147483647
47
P450.01
Freq. preset 1
20.0 Hz
0.0 ... 599.0 Hz
48
P450.02
Freq. preset 2
40.0 Hz
0.0 ... 599.0 Hz
49
P450.03
Freq. preset 3
50.0 Hz* | 60.0 Hz**
0.0 ... 599.0 Hz
50
P450.04
Freq. preset 4
0.0 Hz
0.0 ... 599.0 Hz
* Device for 50-Hz mains    ** Device for 60-Hz mains