Favorites parameter list (default setting)
In the default setting, parameters for resolving typical applications are defined as "Favorites”.
|
No.
|
Display code
|
Name
|
Default setting
|
Setting range
|
Information
|
|
1
|
P100.00
|
Inv. outp. freq.
|
x.x Hz
|
- (Read only)
|
|
|
2
|
P103.00
|
Actual current
|
x.x %
|
- (Read only)
|
|
|
3
|
P106.00
|
Motor voltage
|
x VAC
|
- (Read only)
|
|
|
4
|
P150.00
|
Error code
|
-
|
- (Read only)
|
|
|
5
|
P200.00
|
Control select.
|
Flexible I/O [0]
|
Selection list
|
|
|
6
|
P201.01
|
Freq. setp. src.
|
Analog input 1 [2]
|
Selection list
|
|
|
7
|
P203.01
|
Start method
|
Normal [0]
|
Selection list
|
|
|
8
|
P203.03
|
Stop method
|
Standard ramp [1]
|
Selection list
|
|
|
9
|
P208.01
|
Mains voltage
|
230 Veff [0]
|
Selection list
|
|
|
10
|
P210.00
|
Min. frequency
|
0.0 Hz
|
0.0 ... 599.0 Hz
|
|
|
11
|
P211.00
|
Max. frequency
|
50.0 Hz* | 60.0 Hz**
|
0.0 ... 599.0 Hz
|
|
|
12
|
P220.00
|
Accelerat.time 1
|
5.0 s
|
0.0 ... 3600.0 s
|
|
|
13
|
P221.00
|
Decelerat.time 1
|
5.0 s
|
0.0 ... 3600.0 s
|
|
|
14
|
P300.00
|
Motor ctrl mode
|
VFC open loop [6]
|
Selection list
|
|
|
15
|
P302.00
|
V/f charac.shape
|
Linear [0]
|
Selection list
|
|
|
16
|
P303.01
|
Base voltage
|
type-dependent
|
0 ... 5000 V
|
|
|
17
|
P303.02
|
Base frequency
|
type-dependent
|
0 ... 1500 Hz
|
|
|
18
|
P304.00
|
Limit. rotation
|
Both rot. direct [1]
|
Selection list
|
|
|
19
|
P305.00
|
Switching freq.
|
type-dependent
|
1 ... 33
|
|
|
20
|
P306.01
|
Duty selection
|
Heavy Duty [0]
|
Selection list
|
|
|
21
|
P308.01
|
Max.load.for 60s
|
150 %
|
30 ... 200 %
|
|
|
22
|
P316.01
|
Fixed V/f boost
|
type-dependent
|
0.0 ... 20.0 %
|
|
|
23
|
P323.00
|
Rated mot.curr.
|
type-dependent
|
0.001 ... 500.000 A
|
|
|
24
|
P324.00
|
Max. current
|
200.0 %
|
0.0 ... 3000.0 %
|
|
|
25
|
P400.01
|
Enable inverter
|
TRUE [1]
|
||
|
26
|
P400.02
|
Run
|
Digital input 1 [11]
|
||
|
27
|
P400.03
|
Quick stop
|
Not connected [0]
|
||
|
28
|
P400.04
|
Reset fault
|
Digital input 2 [12]
|
||
|
29
|
P400.05
|
DC braking
|
Not connected [0]
|
||
|
30
|
P400.06
|
Start forward
|
Not connected [0]
|
||
|
31
|
P400.07
|
Start reverse
|
Not connected [0]
|
||
|
32
|
P400.08
|
Run forward
|
Not connected [0]
|
||
|
33
|
P400.09
|
Run reverse
|
Not connected [0]
|
||
|
34
|
P400.13
|
Reverse rot.dir.
|
Digital input 3 [13]
|
||
|
35
|
P400.18
|
Setp: Preset b0
|
Digital input 4 [14]
|
||
|
36
|
P400.19
|
Setp: Preset b1
|
Digital input 5 [15]
|
||
|
37
|
P400.20
|
Setp: Preset b2
|
Not connected [0]
|
||
|
38
|
P420.01
|
Relay function
|
Rdy for operat. [51]
|
Selection list
|
|
|
39
|
P420.02
|
DO1 function
|
Release brake [115]
|
Selection list
|
|
|
40
|
P430.01
|
AI1 input range
|
0 ... 10 VDC [0]
|
Selection list
|
|
|
41
|
P430.02
|
AI1 freq @ min
|
0.0 Hz
|
-1000.0 ... 1000.0 Hz
|
|
|
42
|
P430.03
|
AI1 freq @ max
|
50.0 Hz* | 60.0 Hz**
|
-1000.0 ... 1000.0 Hz
|
|
|
43
|
P440.01
|
AO1 outp. range
|
0 ... 10 VDC [1]
|
Selection list
|
|
|
44
|
P440.02
|
AO1 function
|
Outp. frequency [1]
|
Selection list
|
|
|
45
|
P440.03
|
AO1 min. signal
|
0
|
-2147483648 ... 2147483647
|
|
|
46
|
P440.04
|
AO1 max. signal
|
1000
|
-2147483648 ... 2147483647
|
|
|
47
|
P450.01
|
Freq. preset 1
|
20.0 Hz
|
0.0 ... 599.0 Hz
|
|
|
48
|
P450.02
|
Freq. preset 2
|
40.0 Hz
|
0.0 ... 599.0 Hz
|
|
|
49
|
P450.03
|
Freq. preset 3
|
50.0 Hz* | 60.0 Hz**
|
0.0 ... 599.0 Hz
|
|
|
50
|
P450.04
|
Freq. preset 4
|
0.0 Hz
|
0.0 ... 599.0 Hz
|
|
|
* Device for 50-Hz mains ** Device for 60-Hz mains
|
|
||||