Configure reset behaviour

For some customers it is a common method to always have the same starting conditions of the parameters.
This function allows a user to exclude certain parameter groups from being reset to the default settings using the "Load default settings" device command.
 
Details
By default, all parameters are reset when the default settings are loaded.
The user can reconfigure this function.
Thus, certain parameter groups can be excluded.
The following cannot be selected for the reset:
–
address of the communication bus,
 
–
data format,
 
–
baud rate,
 
–
subnet mask,
 
and for WLAN:
–
channel,
 
–
safety,
 
–
network password,
 
–
SSID name.
 
Your setting values remain stored.
Please make sure that bit 0 must be set to 1 in the parameter 0x2024:001 before executing the default settings in order that the network parameters are excluded from the reset.
Note that the purpose of this function is to enable the master to restore the connection to an inverter after loading the default settings. Because all data mapping and functional settings are reset, the user must let the master reconfigure the settings of the inverter before it operates the inverter.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2024:001
Special settings: Configure default setting
0 ... [0] ... 65535
By default, all parameters are reset when the default settings are loaded (0x2022: 001). The user has the option of reconfiguring this function with the parameter. This allows certain parameter groups to be excluded.
Bit 0
Exclude network
1 = Exclude network parameters:
–
Address of the communication bus, data format, baud rate and subnet mask.
 
–
For WLAN: SSID, passwort, security and channel.
 
Bit 1
Exclude internal registers
1 = Exclude internal registers.