Modbus RTU

Modbus is an internationally approved, asynchronous, serial communication protocol, designed for commercial and industrial automation applications.
 
–
Detailed information on the Modbus can be found on the web page of the international Modbus Organization, USA, who also further develop the Modbus protocol: www.modbus.org
 
–
Information about the dimensioning of a Modbus network can be found in the configuration document for the inverter.
 
 
Details
–
The process of data transmission distinguishes between three different operating modes: Modbus ASCII, Modbus RTU, and Modbus TCP. This chapter describes the Modbus RTU operating mode ("Remote Terminal Unit").
 
–
The Modbus protocol is based on a master/slave architecture where the inverter always works as slave.
 
–
The Modbus network only permits one master sending commands and requests. The master is also the sole instance to be allowed to initiate Modbus communication. No direct communication takes place between the slaves.
 
–
The physical interface corresponds to TIA/EIA-485-A which is very common and suitable for the industrial environment. This interface enables baud rates from 2400 to 115200 kbps.
 
–
The inverter supports Modbus function codes 3, 6, 16 (0x10) and 23 (0x17).
 
 
Typical topology
Line