Mains voltage

The rated mains voltage set for the inverter has an impact on the operating range of the inverter.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2540:001
(P208.01)
Mains settings: Rated mains voltage
(Mains settings: Mains voltage)
–
Setting can only be changed if the inverter is disabled.
 
Selection of the mains voltage for actuating the inverter.
0
230 Veff
1
400 Veff
2
480 Veff
3
120 Veff
5
480 Veff (600 V devices)
6
600 Veff
10
230 Veff/reduced LU level
0x2540:002
(P208.02)
Mains settings: Undervoltage warning threshold
(Mains settings: LU warn. thresh.)
0 ... [0]* ... 1000 V
* Default setting dependent on the model.
Monitoring for undervoltage (LU) in the DC bus: Setting of the warning threshold.
–
If the DC voltage in the DC bus falls below the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:003
(P208.03)
Mains settings: Undervoltage error threshold
(Mains settings: LU error thresh.)
–
Read only: x V
 
Monitoring for undervoltage (LU) in the DC bus: Display of the fixed threshold.
–
If the DC voltage in the DC bus falls below the threshold displayed, the error"" response is triggered.
 
0x2540:004
(P208.04)
Mains settings: Undervoltage reset threshold
(Mains settings: LU reset thresh.)
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus undervoltage.
0x2540:005
(P208.05)
Mains settings: Overvoltage warning threshold
(Mains settings: OU warn. thresh.)
0 ... [0]* ... 1000 V
* Default setting dependent on the model.
Monitoring for overvoltage (OU) in the DC bus: Setting of the warning threshold.
–
If the DC bus voltage exceeds the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:006
(P208.06)
Mains settings: Overvoltage error threshold
(Mains settings: OU error thresh.)
–
Read only: x V
 
Monitoring for overvoltage (OU) in the DC bus: Display of the fixed threshold.
–
If the DC-bus voltage exceeds the threshold displayed, the "Fault" response is triggered.
 
0x2540:007
(P208.07)
Mains settings: Overvoltage reset threshold
(Mains settings: OU reset thresh.)
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus overvoltage.