Skip frequencies
By means of the three parameterisable skip frequencies, critical frequencies can be suppressed which lead to mechanical resonances in the system.
Details
A blocking zone is active as soon as the frequency for this blocking zone is set to a value
≠
"0 Hz".–
The frequency defines the center of the range to be masked out. ①
–
The bandwidth defines its total size. ②
Example: For a blocking zone, the frequency is set to 20 Hz and the bandwidth to 10 Hz. These settings mask out the range from 15 Hz to 25 Hz.
Notes:
–
Skip frequencies are absolute values. With the setting "20 Hz", at the same time also the skip frequency "-20 Hz" is defined.
–
The inverter accelerates/decelerates the motor through the range to be masked out. Continuous operation within this range is not possible.
–
A blocking zone is not active if its bandwidth is set to "0 Hz".
Adjacent and overlapping areas:
–
Example on the left: If the ranges are closely spaced, the ranges are passed through as shown.
–
Example on the right: If the ranges overlap, the lowest and highest value form a new range. In the status display 0x291F:016, both ranges are shown as active.
Valid and invalid ranges:
–
Example on the left: Skip frequency = 5 Hz, bandwidth = 10 Hz
à
Valid range (starts at ≥ 0)–
Example on the right: Skip frequency = 4 Hz, bandwidth = 10 Hz
à
Invalid range (starts at < 0); is thus ignored.Parameter