Configure the digital output 1 as pulse train output
The digital output 1 can be configured for the output of a reference frequency ("pulse train") to transfer an internal actual value signal (e. g. current output frequency or current torque) to a higher-level Controller or other inverters.
Preconditions
In order to output an optimum rectangular signal, a "pulldown" resistor of 1 kOhm is recommended at the digital output. The resistor can be directly connected to the terminals DO1 and GND.
Restrictions
–
When the digital output 1 is configured as pulse train output, this digital output is not available anymore for the output of digital status signals.
–
Minimum output frequency: 1 Hz
–
Maximum output frequency: 10 kHz
Details
Typical applications:
a.
An inverter acts as a master and transfers its current output frequency in the form of a pulse train signal to one or several other inverters (slaves). The slaves use the pulse train signal with a corresponding scaling as a frequency setpoint.
b.
The inverter transfers the current torque or another internal variable as a pulse train signal to a higher-level controller. Then, the controller can evaluate the signal accordingly.
Configuration
In the default setting 0x2644:003 (P423.03) = "Not connected [0]", the digital output 1 is configured as a "normal" digital output: The digital output 1 is controlled with the trigger selected in 0x2634:002 (P420.02).
In order to configure the digital output 1 as pulse train output, the desired signal to be output as pulse train must be selected in 0x2644:003 (P423.03). The trigger assigned to the digital output 1 in 0x2634:002 (P420.02) is then not effective anymore.
The following settings are possible for the pulse train output:
–
Definition of the signal range ①
–
Definition of the output range ②
Diagnostic parameters:
–
The current frequency of the pulse train signal is displayed in 0x2646:001 (P114.01).
Definition of the signal range
The signal range results from the resolution of the selected signal multiplied by the set min and max signal value. Signals outside the signal range are cut off. For examples, see the following table:
|
Signal
|
Resolution
|
Minimum signal
|
Maximum signal
|
Signal range
|
|
Output frequency
|
0.1 Hz
|
0
|
1000
|
0 ... 100.0 Hz
|
|
Frequency setpoint
|
0.1 Hz
|
0
|
1000
|
0 ... 100.0 Hz
|
|
Analog input 1
|
0.1 %
|
0
|
1000
|
0 ... 100.0 %
|
|
Analog input 2
|
0.1 %
|
0
|
1000
|
0 ... 100.0 %
|
|
Motor current
|
0.1 A
|
0
|
100
|
0 ... 10.0 A
|
|
Output power
|
0.001 kW
|
0
|
250
|
0 ... 0.250 kW
|
|
Torque actual value
|
0.1 % *
|
0
|
1000
|
0 ... 100.0 % *
|
|
NetWordIN3
|
0.1 %
|
200
|
500
|
20.0 ... 50.0 %
|
|
NetWordIN4
|
0.1 %
|
0
|
250
|
0 ... 25.0 %
|
|
* 100 % = Rated motor torque 0x6076 (P325.00)
|
||||
Definition of the output range
The frequency output range defined in 0x2644:001 (P423.01) and 0x2644:002 (P423.02) corresponds to the configured signal range.
Configuration examples
Detailed configuration examples can be found in the following subchapters:
Parameter


Example 1: Pulse train 0: ... 10 kHz = output frequency 0 ... 100 Hz