Required commissioning steps

1.
Activate motor control type: 0x2C00 (P300.00) = "Sensorless control (SL PSM) [3]".
 
2.
Carry out optimization of the control loops.
 
–
The default setting enables the operation of a power-adapted motor.
 
–
An optimum operation of this motor control type requires an optimization of the control loops!
 
–
 
 
3.
Optionally: activate the flying restart circuit: 0x2838:001 (P203.01)
 
4.
Optionally for a speed control with torque limitation in operating mode 0x6060 (P301.00) = "MS: Velocity mode [-2]":
 
–
Select the source in 0x2949:001 (P337.01) for the positive torque limit source and set it accordingly.
 
–
Select the source in 0x2949:002 (P337.02) for the negative torque limit source and set it accordingly.
 
 
5.
Optionally for a speed control with torque limitation in operating mode 0x6060 (P301.00) = "CiA: Velocity mode (vl) [2]":
 
–
Set the positive torque limit in 0x60E0
 
–
Set the negative torque limit in 0x60E1.