Generate a connection between inverter and »EASY Starter«

For commissioning the inverter with the »EASY Starter«, a communication link with the inverter is required. This can be established in a wired or wireless manner via WLAN.
 
Preconditions
–
The X16 diagnostic interface (micro USB) is available for wired communication. A USB 2.0 cable (A plug to Micro B plug) is required.
 
–
An inverter with the "WLAN" option is required for wireless communication. In addition, the PC on which the »EASY Starter« is installed must be wireless-enabled.
 
 
Details
The following instructions describe the connection establishment via USB.
The USB interface may only be used temporarily for the diagnostics and parameterization of the inverter. We recommend keeping the inverter and diagnostics device on the same ground potential or disconnecting the diagnostics device from the mains.
 
–
Parameter setting without motor operation does not require a mains voltage. If you connect the inverter directly to the PC without a hub, the USB interface of the PC is sufficient for the voltage supply.
 
–
Instructions for the connection establishment via WLAN can be found in the chapter "Using accessories: WLAN module".
 
How to establish a communication to the inverter via USB:
Preconditions for commissioning:
✓
The functional test described in the mounting and switch-on instructions has been completed successfully (without any errors or faults).
 
✓
The inverter is ready for operation. The mains voltage is switched on.
 
Accessories required for commissioning:
@
The USB 2.0 cable (A-plug on micro B-plug)
 
@
The PC with installed »EASY Starter« software
 
1.
Use a USB cable to connect the inverter to the PC on which »EASY Starter« is installed:
 
a.
Plug the micro B plug of the USB cable into the USB socket.
 
b.
Plug the other end into a free USB type A-socket of the PC.
 
2.
Start »EASY Starter«.
The "Add devices" dialog is shown.
 
3.
Select the "USB onboard" connection.
 
4.
Press Insert button.
 
The »EASY Starter« searches the selected communication path for connected devices. Following successful connection, the inverter is shown in the »EASY Starter« device list. The tabs in »EASY Starter« then provide access to the inverter parameters.