Torque limitation setting
Intro
For torque limitation in VFC mode, a maximum torque can be set for the inverter. If the motor torque exceeds the torque limit, the inverter modifies the output frequency to counteract this exceedance.
The quality of the torque limitation depends on the accuracy of the actual torque calculation.
Preconditions
The VFC torque limiter is only effective for the following motor control types:
–
V/f control (open loop)
–
V/f control (closed loop)
In order to achieve good performance, it is recommended that the motor/inverter first be identified!
Details
The VFC torque limiter becomes active in V/f operation when the current motor torque exceeds the maximum torque. The limiter modifies the output frequency to counteract the exceedance.
The VFC torque limitation functions in a manner similar to the VFC Imax controller, but instead of the total current, the actual torque is taken into account.
When the maximum torque is exceeded:
–
During motor operation, the VFC torque limiter reduces the output frequency.
–
During generator operation, the VFC torque limiter increases the output frequency.
Parameter