Switch/Potentiometer set

The switch/potentiometer set can be used to generate and supply simple control signals via standard I/O.
This example shows a local 2-wire control of the inverter.
–
The potentiometer is connected to analog input 1, which is configured as a setpoint source in the default setting. The potentiometer can be used to vary the frequency setpoint in the range from 0 Hz to the maximum frequency set in 0x2916 (P211.00).
 
–
Switch in FWD position starts the motor in forward direction of rotation.
 
–
Switch in REV position starts the motor in backward direction of rotation.
 
–
Switch in 0 position stops the motor.
 
Connection diagram
Z1, Z2
Potentiometer terminals
FWD 3/4, REV 3/4
Switch terminals
FWD = Run forward (CW)
REV = Run reverse (CCW)
Parameter
Name
Setting for this example
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Run forward (CW)
Digital input 2 [12]
Run reverse (CCW)
Digital input 3 [13]
Reverse rotational direction
Not connected [0]
Activate preset (bit 0)
Not connected [0]
Activate preset (bit 1)
Not connected [0]
①
The "Run" function automatically becomes a "start enable" if the functions "Run forward (CW)"/"Run reverse (CCW)" are connected to triggers. Without start enable, the motor cannot be started.
②
The frequency setpoint is internally led via a ramp generator.  Ramp times