Switch/Potentiometer set
The switch/potentiometer set can be used to generate and supply simple control signals via standard I/O.
This example shows a local 2-wire control of the inverter.
–
The potentiometer is connected to analog input 1, which is configured as a setpoint source in the default setting. The potentiometer can be used to vary the frequency setpoint in the range from 0 Hz to the maximum frequency set in 0x2916 (P211.00).
–
Switch in FWD position starts the motor in forward direction of rotation.
–
Switch in REV position starts the motor in backward direction of rotation.
–
Switch in 0 position stops the motor.
|
Connection diagram
|
|||
|
|
Z1, Z2
|
Potentiometer terminals
|
|
|
FWD 3/4, REV 3/4
|
Switch terminals
FWD = Run forward (CW)
REV = Run reverse (CCW)
|
|
|
|
Parameter
|
Name
|
Setting for this example
|
|
Enable inverter
|
Constant TRUE [1]
|
|
|
Run
|
Digital input 1 [11]
|
|
|
Reset fault
|
Not connected [0]
|
|
|
Run forward (CW)
|
Digital input 2 [12]
|
|
|
Run reverse (CCW)
|
Digital input 3 [13]
|
|
|
Reverse rotational direction
|
Not connected [0]
|
|
|
Activate preset (bit 0)
|
Not connected [0]
|
|
|
Activate preset (bit 1)
|
Not connected [0]
|
|
|
|
|
①
|
The "Run" function automatically becomes a "start enable" if the functions "Run forward (CW)"/"Run reverse (CCW)" are connected to triggers. Without start enable, the motor cannot be started.
|
|
②
|
The frequency setpoint is internally led via a ramp generator.
Ramp times |
Ramp times
Flexible I/O configuration of the start, stop and rotating direction commands