0x2024:002
|
Special settings: Configure STO
0 ... [0] ... 65535
–
Setting can only be changed if the inverter is disabled.
–
From version 05.03
|
Different drive behaviour with reference to the CiA402 state machine.
|
|
Bit 0
|
Activate STO locked
|
0 = After "STO active", the inverter is in the "Ready to switch on [4]" device status.
1 = After "STO active", the inverter is in the "Switch on disabled [3]" device status.
In order to restart the inverter from this device state, the following conditions must be met:
–
No STO activation AND
–
Transition (FALSE ↗ TRUE) of the configured start signal
0 = standard behavior: After STO is activated, the device status changes to “Switched on”.
1 = Behavior as with the i700 servo inverter: After STO is activated, the device status changes to “Switch-on disabled”.
|