0x2639:001
|
Analog output 1: Output range
|
Definition of the output range.
|
|
0
|
Inhibited
|
|
1
|
0 ... 10 VDC
|
|
2
|
0 ... 5 VDC
|
|
3
|
2 ... 10 VDC
|
|
11
|
0 ... 10 VDC (mirrored)
|
In these configurations, negative analog output values are symmetrically mirrored on the Y axis.
|
|
12
|
0 ... 5 VDC (mirrored)
|
|
13
|
2 ... 10 VDC (mirrored)
|
|
0x2639:003
|
Analog output 1: Min. signal
-3276.8 ... [0.0] ... 3276.7
|
Definition of the signal value that corresponds to the minimum value at analog output 1.
Example: configuration of analog output 1 as a 4 ... 20 mA current loop: output current 4 mA = 0x2639:003
|
|
0x2639:004
|
Analog output 1: Max. signal
-3276.8 ... [100.0] ... 3276.7
|
Definition of the signal value that corresponds to the maximum value at analog output 1.
Example: configuration of analog output 1 as a 4 ... 20 mA current loop: output current 20 mA = 0x2639:004
|
|
0x2639:005
|
Analog output 1: Scaled percent value
-327.68 ... [0.00] ... 327.67 %
|
|
|
0x263E:001
|
Activation
|
|
0
|
Off
|
|
1
|
On
|
|
0x263E:002
|
AO1 internal control