Analog output 1

Parameter
Address
Name / setting range / [default setting]
Information
0x2639:001
Analog output 1: Output range
Definition of the output range.
0
Inhibited
1
0 ... 10 VDC
2
0 ... 5 VDC
3
2 ... 10 VDC
11
0 ... 10 VDC (mirrored)
In these configurations, negative analog output values are symmetrically mirrored on the Y axis.
 
12
0 ... 5 VDC (mirrored)
13
2 ... 10 VDC (mirrored)
0x2639:003
Analog output 1: Min. signal
-3276.8 ... [0.0] ... 3276.7
Definition of the signal value that corresponds to the minimum value at analog output 1.
Example: configuration of analog output 1 as a 4 ... 20 mA current loop: output current 4 mA = 0x2639:003
0x2639:004
Analog output 1: Max. signal
-3276.8 ... [100.0] ... 3276.7
Definition of the signal value that corresponds to the maximum value at analog output 1.
Example: configuration of analog output 1 as a 4 ... 20 mA current loop: output current 20 mA = 0x2639:004
0x2639:005
Analog output 1: Scaled percent value
-327.68 ... [0.00] ... 327.67 %
0x263E:001
Activation
0
Off
1
On
0x263E:002
AO1 internal control
-200.00 ... [100.00] ... 200.00 %