Default mapping

The default mapping for the "cyclic sync position mode" is defined in the following parameters:
 
Parameter
Designation
Data type
0x1600
RPDO-->axis: cyclic sync position mode (csp)
RECORD
0x1606
RPDO-->axis: torque limit
RECORD
0x1A00
Axis-->TPDO: cyclic sync position mode (csp)
RECORD
 
Data received from the Controller (RPDO)
Parameter
Designation
Data type
0x6040
CiA402 control word
UNSIGNED_16
0x2830
Lenze control word
UNSIGNED_16
0x6060
Operating mode: selection
INTEGER_8
0x60B2
Torque: offset
INTEGER_16
0x607A
Position: setpoint position
INTEGER_32
0x60B1
Velocity: offset
INTEGER_32
0x2902
Speed controller: load I component
INTEGER_16
0x60E0
Torque: positive limit value
UNSIGNED_16
0x60E1
Torque: negative limit value
UNSIGNED_16
 
Data sent to the Controller (TPDO)
Parameter
Designation
Data type
0x6041
CiA402 status word
UNSIGNED_16
0x2831
Lenze status word
UNSIGNED_16
0x6061
Operating mode: display
INTEGER_8
0x603F
Error code
UNSIGNED_16
0x606C
Velocity: actual velocity
UNSIGNED_16
0x6077
Torque: actual torque
INTEGER_16
0x6064
Position: actual position
INTEGER_32
0x60F4
Following error: actual error
INTEGER_32