Digital output 1

Settings for digital output 1.
 
Digital output 1 is located onboard on terminal X3.
 
 
Details
The digital output 1 is controlled with the trigger selected in 0x2634:002.
The following settings are possible for the digital output:
–
Inversion ①
 
–
Manual I/O control ②
 
Diagnostic parameters:
–
Display of the logic state of the trigger signal:
 
–
Display of the logic state of the digital output: 0x4016:005
 
 
Inversion
The trigger signal of the digital output can be internally inverted logically.
 
Manual I/O control
The digital output can be overridden manually. After the function is activated, the actual values are "frozen". Afterwards, each digital output can be overwritten manually.
Setting:
–
Activation: 0x263C:001
 
–
Entering the manual value: 0x263C:002
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2634:002
Digital outputs function: Digital output 1
Assignment of a trigger to digital output 1.
Trigger = FALSE: X3/DO1 set to LOW level.
Trigger = TRUE: X3/DO1 set to HIGH level.
Notes:
–
An inversion set in 0x2635:002 is taken into consideration here.
 
10
Signal from application
115
Release holding brake
0x2635:002
Inversion of digital outputs: Digital output 1
Inversion of digital output 1
0
Not inverted
1
Inverted
0x4016:005
Digital output 1: Terminal state
–
Read only
 
Display of the logic state of output terminal X3/DO1.
0
FALSE
1
TRUE
0x263C:001
Digital outputs internal control: Activation
Activation of the internal control for all available digital outputs.
0
Off
1
On
0x263C:002
Digital outputs internal control: DO1 internal control
Input of the manual value for the digital outputs.
0
Off
1
On