Basic setting

Preconditions
–
The wired communication with the inverter has been established.
 
–
If this condition is not met, read more detailed notes in section "Generate a connection between inverter and »EASY Starter«". 
 
 
–
The PC with the installed
»
EASY Starter
«
is started.
 
 
Automatic configuration
By default, the engineering port of the inverter receives its IP address automatically from a DHCP server. By pressing the "DHCP" button, the (→) parameter is active ("enabled").
Now, the IP configuration is completed. The inverter can be accessed via the Ethernet connection.
 
Manual configuration
Make sure to press the "Restart with current values" button every time you change the values.
 
The engineering port must be configured when a static address is to be assigned.
For this purpose, the "DHCP" button must bet set to the "Disabled" state.
The following parameters can be entered in the
»
EASY Starter
«
:
–
IP address
 
–
Network mask
 
–
Gateway address
 
 
Using a configuration file
A file named "ip.txt" can be used to reset the IP address. This file must be stored on the SD card in the root directory.
The network settings are evaluated and accepted when the inverter is started. The file is then renamed as "ip_old.txt".
The structure of the text file can look as follows:
–
192.168.101.221
 
–
255.255.255.0
 
–
192.168.101.1
 
If the static IP address is to be reset to DHCP, only the content of the ip.txt file must be set to "DHCP". This serves to use DCHP for a dynamic address allocation at next boot.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2450
Engineering port control
Acceptance of the current settings (0x2451:xxx) for the engineering port.
0
No action/No error
Only status feedback
1
Restart with current values
Restart the device to apply the current settings.
10
Busy
Only status feedback
11
Action cancelled
12
Faulted
0x2451:001
Engineering port settings: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Setting of the IP address.
0x2451:002
Engineering port settings: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Setting of the subnet mask.
0x2451:003
Engineering port settings: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Setting of the gateway address.
0x2451:004
Engineering port settings: DHCP
Use (enable) of the Dynamic Host Configuration Protocol (DHCP).
0
Disabled
1
Enabled
0x2451:007
Engineering port settings: DNS server address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
0x245B:001
System time: Setting method
Changes are only applied after a restart with current values: 0x245A:001 = [1].
0
NTP server
NTP synchronization
Network Time Protocol (Standard for the synchronization of clocks in computer systems)
Note!
–
NTP server addresses must be defined in 0x245A.
 
–
An NTP server must send the current system time via Ethernet.
 
–
The sent system time is automatically adopted.
 
1
EtherCAT Distributed Clocks
EtherCAT Distributed Clocks synchronization
Note!
–
The Distributed Clocks synchronization must be active.
 
–
The system time of the higher-level controller is automatically adopted.
 
2
Manual input
No automatic synchronization
Note!
The time entered manually in 0x2452B:002 is adopted as the system time.
0x245B:002
System time: Current time
0 ... [ ] ... 18446744073709551615 ns
–
0x245B:001 = 0 or 1:
 
–
Display of the current synchronized system time
 
 
–
0x245B:001 = 2:
 
–
Manual timing
 
–
Format: TT/MM/YY HH:MM:SS.ms
 
–
The system time is recalculated after each mains switching New system time = last stored time + value of the switch-on hour counter