Basic setting
Preconditions
–
The wired communication with the inverter has been established.
–
If this condition is not met, read more detailed notes in section "Generate a connection between inverter and »EASY Starter«".
–
The PC with the installed
»
EASY Starter«
is started.Automatic configuration
By default, the engineering port of the inverter receives its IP address automatically from a DHCP server. By pressing the "DHCP" button, the (→) parameter is active ("enabled").
Now, the IP configuration is completed. The inverter can be accessed via the Ethernet connection.
Manual configuration
Make sure to press the "Restart with current values" button every time you change the values.
The engineering port must be configured when a static address is to be assigned.
For this purpose, the "DHCP" button must bet set to the "Disabled" state.
The following parameters can be entered in the
»
EASY Starter«
:–
IP address
–
Network mask
–
Gateway address
Using a configuration file
A file named "ip.txt" can be used to reset the IP address. This file must be stored on the SD card in the root directory.
The network settings are evaluated and accepted when the inverter is started. The file is then renamed as "ip_old.txt".
The structure of the text file can look as follows:
–
192.168.101.221
–
255.255.255.0
–
192.168.101.1
If the static IP address is to be reset to DHCP, only the content of the ip.txt file must be set to "DHCP". This serves to use DCHP for a dynamic address allocation at next boot.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2450
|
Engineering port control
|
Acceptance of the current settings (0x2451:xxx) for the engineering port.
|
|
|
0
|
No action/No error
|
Only status feedback
|
|
|
1
|
Restart with current values
|
Restart the device to apply the current settings.
|
|
|
10
|
Busy
|
Only status feedback
|
|
|
11
|
Action cancelled
|
||
|
12
|
Faulted
|
||
|
0x2451:001
|
Engineering port settings: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
|
Setting of the IP address.
|
|
|
0x2451:002
|
Engineering port settings: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
|
Setting of the subnet mask.
|
|
|
0x2451:003
|
Engineering port settings: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
|
Setting of the gateway address.
|
|
|
0x2451:004
|
Engineering port settings: DHCP
|
Use (enable) of the Dynamic Host Configuration Protocol (DHCP).
|
|
|
0
|
Disabled
|
||
|
1
|
Enabled
|
||
|
0x2451:007
|
Engineering port settings: DNS server address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
|
||
|
0x245B:001
|
System time: Setting method
|
Changes are only applied after a restart with current values: 0x245A:001 = [1].
|
|
|
0
|
NTP server
|
NTP synchronization
Network Time Protocol (Standard for the synchronization of clocks in computer systems)
Note!
–
NTP server addresses must be defined in 0x245A.
–
An NTP server must send the current system time via Ethernet.
–
The sent system time is automatically adopted.
|
|
|
1
|
EtherCAT Distributed Clocks
|
EtherCAT Distributed Clocks synchronization
Note!
–
The Distributed Clocks synchronization must be active.
–
The system time of the higher-level controller is automatically adopted.
|
|
|
2
|
Manual input
|
No automatic synchronization
Note!
The time entered manually in 0x2452B:002 is adopted as the system time.
|
|
|
0x245B:002
|
System time: Current time
0 ... [ ] ... 18446744073709551615 ns
|
–
–
0x245B:001 = 2:
– Manual timing – Format: TT/MM/YY HH:MM:SS.ms – The system time is recalculated after each mains switching New system time = last stored time + value of the switch-on hour counter |
|