Compensating for inverter influence
When inserting a motor from the motor catalog, the inverter characteristic curve for the selected motor is automatically loaded. This process is independent of the control type.
Exception:
–
Enter nameplate data
–
Manual entry
–
Identification run
In this case, no inverter characteristic curve is loaded. You must determine the inverter characteristic curve manually.
Determine inverter characteristic manually
The started procedure can be canceled at any time with the inverter disable. Characteristic values that have already been determined are discarded.
How to determine the inverter characteristic curve:
1.
Disable inverter.
2.
Switch to the "Inverter characteristic curve: Identification" operating mode.
0x2825 = 8
0x2825 = 83.
Enable inverter.
The procedure starts.
After successful completion, the inverter is disabled. The points of the determined inverter characteristic curve are written into the table. 0x2947
If errors occur during the process, the procedure is aborted. Characteristic values that have already been determined are discarded.
After successful completion, the inverter is disabled. The points of the determined inverter characteristic curve are written into the table. 0x2947
If errors occur during the process, the procedure is aborted. Characteristic values that have already been determined are discarded.
4.
Save changed settings.
5.
The inverter disable set by the procedure can be canceled via the control word.
0x6040 = 7
0x6040 = 7Manual determination of the inverter characteristic curve is complete.
Parameter