Current safety instructions for known error patterns
Important information on the safe output in conjunction with the "SOS observed" signal
for i950 Extended Safety
for i950 Extended Safety
The following faulty behavior of the safe digital output SD-Out1 (terminal X82, O1A, O1B) was detected in conjunction with the "SOS observed" signal during the "Safe operational stop (SOS)" safety function:
Contrary to the intended behavior, the signal of the safe digital output does not follow the status signal "SOS observed" when leaving the SOS tolerance limits.
The affected safety function is located in all i950 cabinet inverters with "Extended Safety" (type code I95AExxxxxCxxxxxxxxx).
The malfunction can be rectified by updating the safety firmware free of charge, which can only be carried out by Lenze technical support.
Measures required:
–
If the "SOS observed" signal is used via the safe digital output or is to be used in future, the correction must be made by means of a firmware update. The function must be deactivated until the firmware update has been carried out.
–
Please contact your regional technical support to carry out the firmware update required to rectify the malfunction.