Product description
Product identification
This documentation applies to the m300 Lenze Smart Motor product familyconsists of the following components and their identification:
Name of product and product ID
|
Name of product |
Product ID |
|---|---|
|
m300 Lenze Smart Motor |
MSEMAxxxxx-xx |
Name of accessories
|
Name of accessory |
Product ID |
|---|---|
|
Lenze Smart Motor App |
Android Play Store / Lenze Smart Motor |
|
EASY Starter |
refer to chapter EASY Starter |
|
Conoverter USB -> NFC |
EZAETF001 |
Location in the network
These components are located in the automation pyramid at the control level. Furthermore, they are located in the security zone "CAP-Field" (Zones and conduits).
Location in the Network
The components addressed here have two relevant interfaces:
-
Conduit: Field Level
The Field Level interface refers to the three digital inputs and one digital output. With the help of the inputs, the user can specify the defined speeds and receive information about an existing error via the output. These interfaces are negligible from a cyber security point of view as they do not support any data protocols.
-
Conduit: Engineering
The m300 Lenze Smart Motor has a smart interface via NFC (near field communication) to carry out parameterization in two ways. Way (a) refers to the use of a Smart Motor App and the NFC function of a smartphone, way (b) refers to the use of an EASY Engineering Tools Starter and simultaneous use of a USB -> NFC adapter.
Intended purpose
The intended use of these components is described in the application as directed and can be found in the operating instructions for the respective component. In the following, some specifics regarding Cyber Security are discussed.
-
These components are professional equipment and may only be commissioned and decommissioned by specialists.
-
These components also require maintenance during their life cycle, which must be carried out by the operator.
-
Modifications to the firmware, software or hardware of the components are not permitted.
-
If these components are taken out of operation or disposed of, the instructions here in the documentation must be observed.
Intended environment
The intended environment for these components is described in the application as directed and can be found in the operating instructions for the respective component. In the following, some specifics regarding Cyber Security are discussed.
-
As these components are decentralized, a closed control cabinet is out of the question. Therefore, physical access protection is required.
-
The components are not operated directly on the open Internet, but must also be operated by the operator via protection systems such as firewall, IDS, IPS, … .
-
Deactivate all unused interfaces and/or protocols, both for the components mentioned here and for all components that are connected to the network.
-
The more security-critical an application is, the more systems should be separated. Only combine tasks on one component if they are in the same risk classification.
-
Wherever possible, use a Defense-in-Depth Concept in the environment of this component.
-
Use appropriate authentication mechanisms. This applies, for example, to passwords that have the necessary complexity and an appropriate life cycle. The current state of the art must be taken into account here.
-
Handle secrets, such as passwords, appropriately. The focus here is on the handling of secrets on the components noted here, but also on the data stored in the environment of these components.
-
Validate all input options for validity. Pay attention to all human user interfaces as well as the machine software interfaces.
-
Evaluate the environment, the technical task to be performed and the existing component security in a security-critical consideration and assess whether additional protective measures are necessary for your application.
Security key indicators
Security key indicator (in accordance with IEC 62443-4-2):
-
These components are considered embedded devices (EDR).
-
These components have a security level of SL-C 0, because no certification was carried out.
-
These components have the technical functionality to enable an SL-vector from SL-C(m300)={ IAC=0; UC=0; SI=0; DC=0; RDF=0; TRE=0; RA=0 }.