PLC-Designer UDP Communication

Name of Protocol

PLC Designer UDP Communication

Purpose

This protocol is used to run the network scan and the communication between »PLC Designer« and Controller.

Ports

udp/1740 … 1743

Architecture

This communication is based on the UDP communication.

ISO/OSI Model

Ein Bild, das Text, Diagramm, Screenshot, parallel enthält.

Automatisch generierte Beschreibung

PLC Designer UDP Communication in the ISO/OSI Model

Scan Network

Ein Bild, das Text, Schrift, Reihe, Screenshot enthält.

Automatisch generierte Beschreibung

Scan Network

The »PLC Designer« is installed on a computer with an exemplary IP address of 192.168.5.4.This requests the network via UDP protocol on port 1743 and requests the broadcast IP address in the subnet on 92.168.5.255 on ports 1740, 1741, 1742, 1743 in sequence. Existing devices, in this example 192.168.5.99, will respond via port 1740 and thus expose themselves to the network scan.

Communication

After performing a network scan, you can access the controller online. Here we use the previously scanned UDP connection.

Ein Bild, das Text, Screenshot, Schrift, Reihe enthält.

Automatisch generierte Beschreibung

UDP Communication