x5x0.OPCUAClient.Certificate

OPC UA Secure Communication Compatibility Notice (x5x0 / IXrouter3)

Important Notice regarding OPC UA Secure Communication:

Starting with Controller Firmware v2.0, OPC UA communication is configured to use encrypted communication (Sign & Encrypt) by default. The Lenze x5x0 gateway is based on the IXON IXrouter3 platform. The IXrouter3 does not support OPC UA communication using the Sign & Encrypt security mode and this capability will not be added to the product. As a result, a secure OPC UA connection between a Controller configured for Sign & Encrypt and an IXrouter3-based x5x0 cannot be established.

To enable OPC UA communication, one of the following measures must be taken:

  • Replace the IXrouter3-based x5x0 with an IXON SecureEdge device, which supports OPC UA Sign & Encrypt.

  • Disable OPC UA encryption on the controller and use a compatible security configuration.

Customers planning to use encrypted OPC UA communication are recommended to use the IXON SecureEdge platform.

For further information on IXON connectivity solutions, refer to the IXON Connectivity Platform.