Display of error messages in the logbook
Errors and messages are listed historically in the logbook.
The memory of the logbook is limited. If the memory is full, the oldest message in the logbook is deleted when a new message is received.
A certain memory size is available for this logbook; if this is exceeded, old messages are deleted.
New messages are not automatically displayed in the logbook. The messages in the logbook are only updated by a trigger.
Trigger in the diagnostic visualisation:
Trigger in the "PLC Designer":
Structure of the logbook entry
|
Number |
Number of total messages in the logbook |
|
Time (UTC) |
Time of occurrence of the error: Date in UTC, time |
|
Counter |
Number of times the error has occurred in immediate succession. |
|
Severity |
|
|
Event ID |
|
|
Error Text |
Individual text for the event, which is uniquely described by the two 16-bit part IDs. |
|
Component name |
Unique name of the component in the control unit. |
|
Component Type |
Grouping of components such as EtherCAT slaves, motion axes, etc. The differentiation is helpful for using the filters. |
|
Layer |
Structure of the control unit and its functions:
|
Severity of the error that has occurred
Error messages of severity FAULT, TROUBLE or WARNING_LOCK must be acknowledged.
Error messages with a WARNING severity level do not have to be acknowledged. The error message is automatically reset when the trigger condition is no longer present.
For Lenze components, the severity levels can be linked to reactions (example: FAULT_CINH = fault with controller inhibit).
|
Symbol |
Event type |
Description of the |
|---|---|---|
|
|
FAULT TROUBLE |
The trigger condition is met. |
|
|
FAULT TROUBLE |
The trigger condition is no longer present. The error message can be acknowledged. After acknowledgement, the error message is no longer displayed. |
|
|
WARNING_LOCK WARNING |
The trigger condition is met. |
|
|
WARNING_LOCK |
The trigger condition is no longer present. The error message can be acknowledged. After acknowledgement, the error message is no longer displayed. |
|
|
INFO |
An information is available. |
The event ID is made up of two pieces of 16-bit information.
|
Central Text-Ref-ID for a component |
Fixed text ref IDs for Lenze error messages. The TextREF IDs 0x3c00 … 0x3fff are available for individual use. |
|
Individual ID-part for the event of the component |
Freely available IDs that can be assigned for your own error messages in PLC programming. |