Features and capabilities

The Lenze OPC UA PubSub on the controller supports the following service capabilities. The individually listed capabilities have the limit named here. Depending on the combination and utilization of these capabilities, as well as the utilization of the CPU due to the PLC application and other processes on the controller, the controller may reach its performance limit.

This must be considered during project engineering.

PubSub Feature / Capabilitiy1)

c430

c520, c550

Data Access

Primitive and structured UA Server variables and arrays from PLCopen and User Information model.

Quality

None Realtime

Protocols

UDP (UADP)

UDP (UADP)

MQTT (UADP)5)

MQTT (JSON)5)

Routing schemes

Unicast and Multicast

Security4)

None

Sign

Sign&Encrypt

Sum of Maximum number of connections

2

4

Sum of Maximum number of WriterGroups

4

8

Sum of Maximum number of ReaderGroups

4

8

Sum of Maximum number of Writers

8

16

Sum of Maximum number of Readers

8

16

Sum of Maximum number of datasets2)

8

16

Minimum publishing interval

100 ms

50 ms

Maximum NetworkMessage size3)

1400 byte

1400 byte

1)

For the OPC UA PubSub functionality a Lenze Licence is needed. The activation of OPC UA licence packages can be done via the Lenze Licence Manager.

2)

There is no limitation of the number of nodes in a DataSet. Just the NetworkMessage size limits the payload.

3)

Maximum NetworkMessage size for all variable values of a WriterGroup or ReaderGroup

4)

Security just for UDP (UADP) protocol with SKS keys

5)

MQTT, without transport security (TLS) and without Web Socket.