Task cycle time
The cycle time of the task in which the L_TP2P_TemperatureControlBase function block is used has to be adjusted to the PWM period ( lrPWMPeriod parameter). Here, the ratio of the times has to be at least 1:100.
Example: In case of a standard PWM period of 1.0 s, the task cycle time must be £ 10 ms.
If the ratio of the PWM period to the task cycle time is less than 1:50, the eErrorID output displays the warning "17134" (TaskCyclePWMPeriodMismatch).