Temperature control with differential actuator
An application example is a control valve with a 3-point drive which controls the flow of a medium. Such a valve is controlled via 2 electrical connections ("OPEN"; "CLOSED") which directly drive an actuating motor.
-
"OPEN" activated (controller output xDiffPositiveOut = TRUE): Valve opens/is opened.
-
"OFF" activated (controller output xDiffNegativeOut = TRUE): Valve closes/is closed.
If neither of the connections are controlled ( xDiffPositiveOut or xDiffNegativeOut = FALSE , the valve rests in its current position.
The valve position is determined using the runtime of the valve. The runtime is the time the valve drive needs to move the valve from the CLOSED end position to the OPEN end position. The runtime is typically about 60 ... 180 s for valves in heating systems. The runtime is configured in lrDiffCtrlActuatingTime .
Notes on the control process
-
Since the lrDiffCtrlActuatingTime parameter is a control valve parameter due to the design, it cannot be determined by automatic control parameter identification. It must be determined at least approximately from the technical data, or it can be determined experimentally.
-
In order to reduce the strain on the electromechanical components (actuator, relay, etc.), the lrDiffCtrlSignalTimeMin and lrDiffCtrlBreakTimeMin parameters can be used to specify individual minimum times for the pulse and break duration for the two signals, xDiffPositiveOut and xDiffNegativeOut .