Heatsink temperature monitoring

Parameter
Address
Name / setting range / [default setting]
Information
0x2D84:001
(P117.01)
Heatsink temperature: Heatsink temperature
(Heatsink temp.: Heatsink temp.)
–
Read only: x.x °C
 
Display of the current heatsink temperature.
0x2D84:002
Heatsink temperature: Warning threshold
50.0 ... [80.0]* ... 100.0 °C
* Default setting dependent on the model.
Warning threshold for temperature monitoring.
–
If the heatsink temperature exceeds the threshold set here, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of approx. 5 °C.
 
–
If the heatsink temperature increases further and exceeds the non-adjustable error threshold (100 °C), the inverter changes to the "Fault" device status. The inverter is disabled and thus any further operation is stopped.