Monitoring
The parameters for setting network monitoring functions are described below.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2858:001
(P515.01)
|
Modbus monitoring: Response to time-out
(Modbus monit.: Resp. Time-out)
|
Selection of the response executed if no valid messages have been received via the Modbus for a longer time than the time-out period set in 0x2858:002 (P515.02).
|
|
|
0
|
No response
|
||
|
1
|
Warning
|
||
|
2
|
Trouble
|
||
|
3
|
Fault
|
||
|
0x2858:002
(P515.02)
|
Modbus monitoring: Time-out time
(Modbus monit.: Time-out time)
0.0 ... [2.0] ... 300.0 s
|
Time-out period for monitoring the message reception via Modbus.
|
|
Severity