Monitoring

The parameters for setting network monitoring functions are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2859:001
(P515.01)
PROFINET monitoring: Watchdog elapsed
(PROFINET monit.: WD elapsed)
–
From version 02.00
 
Selection of the response to a permanent interruption of the communication to the IO controller.
Corresponding error code: 33168 | 0x8190 "PROFINET: Watchdog time-out"
Associated event ID:
–
33168 | 0x8190 - Network - Watchdog time-out
 
0
No response
1
Warning
2
Trouble
3
Fault
0x2859:002
(P515.02)
PROFINET monitoring: Data exchange exited
(PROFINET monit.: Data exch.exited)
Selection of the response to exiting the "Data Exchange" state.
0
No response
1
Warning
2
Trouble
3
Fault
0x2859:003
(P515.03)
PROFINET monitoring: Invalid configuration
(PROFINET monit.: Invalid config)
–
From version 02.00
 
Selection of the response triggered by the reception of invalid configuration data.
Associated event ID:
–
33414 | 0x8286 - Network - PDO mapping error
 
0
No response
1
Warning
2
Trouble
3
Fault
0x2859:004
(P515.04)
PROFINET monitoring: Initialisation error
(PROFINET monit.: Init. error)
–
From version 02.00
 
Selection of the response triggered by the occurrence of an error during the initialisation of the network component.
Associated event ID:
–
33170 | 0x8192 - Network - Initialization error
 
0
No response
1
Warning
2
Trouble
3
Fault
0x2859:005
(P515.05)
PROFINET monitoring: Invalid process data
(PROFINET monit.: Inval. proc.data)
–
From version 02.00
 
Process data marked as invalid (IOPS is "BAD") are received by the IO Controller. Typically in case of
–
a PLC in STOP state,
 
–
alarms,
 
–
acyclic demand data.
 
Selection of the response triggered by the reception of invalid process data.
Associated event ID:
–
33171 | 0x8193 - Network - Invalid cyclic process data
 
0
No response
1
Warning
2
Trouble
3
Fault