"CAP-Machine" Zone
The abbreviation CAP Machine means "Core Automation Platform Machine". This zone contains components that are installed in the machine at runtime. This security zone must be protected by the operator of the automation system for authorized access. This refers to the authorization of data-technical access, but also to the authorization of human access on site. For example, the components must be protected against mechanical manipulation or removal of storage media. In addition, all these components have a communication interface with the machine's Ethernet. For this reason, these components are placed in a security zone and the same security level target requirements (SL-T) apply here. This zone has four conduits.
‘IT/OT Gateway’ conduit
This conduit connects the Security zone "CAP Machine" with the "Production Zone". This conduit is not generalizable and looks different in different installations, depending on the network configuration. This is typically where the transition from OT (operational technology) to IT (information technology) occcurs. From a cyber security perspective, this transition needs to be considered particularly carefully. We recommend assessing risks based on the Golden Rules for Secure Systems (refer to chapter ‘Cyber Security/Security strategy/Golden rules for secure systems’), e.g.:
-
Minimize Attack Surface: Separate network segments and use NAT technologies
-
Separate Systems: Not only separate the IT from the OT technology, but also separate machines from each other.
"Fieldbus" conduit
This conduit connects the security zone "CAP Machine" with the "Production Zone". When integrating the machine into production, a special focus must also be placed on this interface. This is necessary for two reasons.
Firstly, standardized fieldbus systems are used here, which in most cases have not implemented cyber security requirements. These must be classified as SL-0 and included accordingly in the risk assessment during system design.
Secondly, the standardized Ethernet TCP/UDP channel can be used in parallel with some proprietary fieldbus systems. This must be considered separately and taken into account in the cyber security risk assessment during system design.
"Tools" conduit
This conduit connects the security zone "CAP Machine" with the "CAP Tools".It only exists during the commissioning or maintenance of the machine. Here, the system design must be taken into account in the risk assessment to ensure that the accesses are authorized and the employees have been instructed on the components and the machine cyber security concept. Furthermore, it must be ensured that the computer systems on which the necessary tools are installed must comply with the current cybersecurity requirements and correspond to the current state of cybersecurity.
"Field" conduit
This conduit connects the security zone "CAP Machine" with the "CAP Field". The special feature here is the cyber security consideration of the field components. These components are connected via EtherCAT the communication medium and thus represent only a low level of protection in terms of cyber security. The operator must therefore ensure that no unauthorized access to the components can take place.