Data consistency

The Lenze OPC UA Server accesses the PLC variables internally and displays them in its information model depending on the configuration.

Data consistency is only guaranteed for elementary data types up to 8 bytes in size. This does not apply to strings. With structures and arrays, the individual underlying variables are accessed so that these are also consistent. However, it is not guaranteed that the complete structure or array is consistent in itself.

This data consistency on elementary data types up to 8 bytes is sufficient for the vast majority of use cases.

  • In a visualization it could happen that a value is inconsistent for a short moment. In the next moment, however, this value is displayed correctly.

  • With clock-based machines, synchronization can be guaranteed applicatively via an additional variable that is used by the server and client application for a handshake. This means that there are no problems in this case either.