SF_CTD (FB)

Description of the function block
[Tip] Tip

The version of the function block as described here corresponds to the latest version of the function block in Version list of function blocks.

[Tip] Tip

SF_CTD is a counter block from the SafetyStandard library. It is an extension of CTD, a standard IEC 61131-3 function block. The SF_CTD function block contains both standard data types and safety-related data types (prefix: SAFE).

SF_CTD fulfills the countdown function.

Figure 110. Function block: SF_CTD

Function block: SF_CTD

Table 84. VAR_INPUT

Name

Data Type

Initial Value

Description, parameter values

CD

BOOL

FALSE

Rising edge at CD decrements CV by 1.

LOAD

BOOL

FALSE

TRUE: Sets CV to the initial value PV

FALSE: Counting down is enabled.

PV

SAFEINT

0

Start value (upper limit) for counting down CV.


Table 85. VAR_OUTPUT

Name

Data Type

Initial Value

Description, parameter values

Q

SAFEBOOL

FALSE

Becomes TRUE when CV reaches 0.

CV

SAFEINT

0

Current counter value. From the start value, PV is decremented step by step by 1 until 0 is reached.


FB code

IF LOAD THEN CV := PV;
ELSIF CD AND (CV > PVmin)
    THEN CV := CV-1;
END_IF ;
Q := (CV <= 0) ;

The numerical value of PVmin is 0.