Object: Alarm Configuration

Symbol: _vis_icon_alarmconfiguration.png

The alarms are managed in the Alarm Configuration object.

When you insert the object, the following default objects are also inserted automatically:

  • Alarm class: Error

  • Alarm class: Info

  • Alarm class: Warning

  • Alarm storage: AlarmStorage

You can use these objects, but you don't have to. You can delete them and replace them by objects that you add yourself.

Alarm instances

List with alarm instances of the AlarmGroupInstances alarm group

Variable

Function block instance or structure variable for which an alarm definition exists

Example: PLC_PRG.fb1Test

Alarm Group Template

Alarm group template (usually from a library)

Example: AGT_FB_1

Alarm Group

Alarm group in which the alarm instance is implicitly included.

Create

_vis_icon_checkedbox.png: The alarms of this instance are created.

Button: Create or update alarm instances

If new IEC code has been created in the project and new instances have been added, then the alarm configuration requires an update. Click the button to create or update the alarm instances. Then IEC programming and alarm configuration match again.

If, for example, another library has been inserted or function block instances are created from this library without changing the alarm configuration, then the list of alarm instances needs to be updated.

Check alarm instances during compilation

_vis_icon_checkedbox.png: Enabled by default

Automatically checks the list of alarm instances for completeness and correctness during compilation and issues a message. The alarm configuration then has to be updated by means of the Create or update alarm instances button.

It is checked whether or not all instances of function blocks and all variables of structures with AlarmGroupTemplate are covered.