Logbook
The devices are equipped with a logbook function which records system events and error messages. The entries in the logbook make it easier to diagnose the automation system.
The following information is processed by the logbook:
–
Error messages and events of the application are displayed.
–
Error messages and events of the application are saved on the SD card.
The logbook of the controller can be accessed via the
»
PLC-Designer«
.The event currently active in the controller can also be retrieved via the event monitor.
PLC diagnostics
PLC diagnostics Structure of a logbook entry
A logbook entry consists of the following information:
–
Ascending numbering of the logbook entry
–
Date / time of the logbook entry
–
Application triggering the logbook entry
–
Severity of the event in four categories
–
Information
–
Warning
–
Fault
–
Error
–
Area as the event origin of the triggered error message.
Logbook entry "unknown event"
If the entry "unknown event" is displayed in the logbook, this may have the following causes:
|
Cause
|
Remedy
|
|
Incorrect description of the error in the application
|
Check application
|
|
Old project runs on newer firmware
|
Update project to the firmware version of the controller
|
|
Missing error description in the device descriptions
|
Contact the manufacturer
|
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2022:015
|
Device commands: Delete logbook
|
All entries in the logbook are deleted.
–
When the device command has been executed successfully, the value 0 is shown.
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
|
|
|
0
|
Off / ready
|
Only status feedback
|
|
|
1
|
On / start
|
Execute device command
|
|
|
2
|
In progress
|
Only status feedback
|
|
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (Device disabled)
|
||
|
0x2022:036
|
Device commands: Export Logbook
|
Exports the logbook for the upload into the engineering tools.
–
When the device command has been executed successfully, the value 0 is shown.
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
|
|
|
0
|
Off / ready
|
Only status feedback
|
|
|
1
|
On / start
|
Execute device command
|
|
|
2
|
In progress
|
Only status feedback
|
|
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (Device disabled)
|
||
|
0x2022:037
|
Device commands: Delete Logfiles
|
Deletion of log files on the device that were exported in an earlier step via 0x2022:036 (Export Logbook).
–
When the device command has been executed successfully, the value 0 is shown.
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
|
|
|
0
|
Off / ready
|
Only status feedback
|
|
|
1
|
On / start
|
Execute device command
|
|
|
2
|
In progress
|
Only status feedback
|
|
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (Device disabled)
|
||