Logbook

The devices are equipped with a logbook function which records system events and error messages. The entries in the logbook make it easier to diagnose the automation system.
The following information is processed by the logbook:
–
Error messages and events of the application are displayed.
 
–
Error messages and events of the application are saved on the SD card.
 
The logbook of the controller can be accessed via the
»
PLC-Designer
«
.
The event currently active in the controller can also be retrieved via the event monitor. PLC diagnostics
 
Structure of a logbook entry
A logbook entry consists of the following information:
–
Ascending numbering of the logbook entry
 
–
Date / time of the logbook entry
 
–
Application triggering the logbook entry
 
–
Severity of the event in four categories
 
–
Information
 
–
Warning
 
–
Fault
 
–
Error
 
 
–
Area as the event origin of the triggered error message.
 
 
Logbook entry "unknown event"
If the entry "unknown event" is displayed in the logbook, this may have the following causes:
Cause
Remedy
Incorrect description of the error in the application
Check application
Old project runs on newer firmware
Update project to the firmware version of the controller
Missing error description in the device descriptions
Contact the manufacturer
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2022:015
Device commands: Delete logbook
All entries in the logbook are deleted.
–
When the device command has been executed successfully, the value 0 is shown.
 
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
 
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2022:036
Device commands: Export Logbook
Exports the logbook for the upload into the engineering tools.
–
When the device command has been executed successfully, the value 0 is shown.
 
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
 
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2022:037
Device commands: Delete Logfiles
Deletion of log files on the device that were exported in an earlier step via 0x2022:036 (Export Logbook).
–
When the device command has been executed successfully, the value 0 is shown.
 
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
 
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)