Start/stop application

Application credit may be required to execute the PLC application.
When the application is compiled, the required application credit is determined. The value is entered in the following parameters. 0x2013:002
Insufficient application credit results in the application being executed with a delay. Please contact your Lenze service center if you require additional application credit.
 
 
The PLC application is controlled using the following device commands:
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2022:044
Device commands: Start PLC application
–
When the device command has been executed successfully, the value 0 is shown.
 
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
 
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2022:045
Device commands: Stop PLC application
–
When the device command has been executed successfully, the value 0 is shown.
 
–
Do not switch off the supply voltage or remove the SD card from the controller while the device command is being executed.
 
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)