Configuration files

The configurations whether certain EtherCAT slaves are mandatory or optional, are summarized in the "mmc-0-conf.csv" text file on the controller. More identifying features of the slaves are included in the text file "mmc-0-ident.csv".
Storage directory:
/SDCard/IPC/PLC
The machine configuration "mmc-0-conf.csv" and the identifying features "mmc-0-ident.csv" are only loaded when a project is loaded.
If an error occurs during the initialization process, a corresponding error message including the line number is output in the controller logbook.
 
 
Machine configuration
The machine configuration file "mmc-0-conf.csv" consists of a matrix. All EtherCAT slaves are given horizontally in ascending order, the individual configurations are given vertically. The EtherCAT slaves are referenced based on the EtherCAT address (Fixed Address), the configuration is based on the designator (STRING). If a slave has to be contained in a configuration (Mandatory Slave), it is marked by an 'X' in the following sample table.
Address
1001
1002
1003
Inverter
i700
9400 CiA
9400 AS
Configuration 1: All inverters are configured.
X
X
X
Configuration 2: The 1st and 2nd inverters are configured.
X
X
Configuration 3: The 1st and 3rd inverters are configured.
X
X
The configuration file does not necessarily have to be available.
Preconditions:
–
Manual address assignment via the L_ETC_MMCAssignAddress function block
 
–
Operation of the EtherCAT master in the "RUN_WITHOUT_CHECK" mode
 
 
Further identification features of the EtherCAT slaves
An EtherCAT slave is identified by the following features:
–
Vendor-ID/Product Code/Revision
 
–
Second Station Address (alias address)
 
–
ID selector (is not supported)
 
Moreover, the modular machine configuration makes it possible to use CoE objects for further identification of the EtherCAT slaves. These additional identification features are contained in the "mmc-0-ident.csv" text file. If the identification file is not available on the Lenze controller, no identification features are used.
The structure of the text file "mmc-0-ident.csv" is strictly defined. All columns must be provided in the order specified or may contain an empty string. The EtherCAT slaves are arranged in ascending order of their address according to the sample table.
Name
Address
Index
Subindex
Type
Data
L_i700_SM
1001
1001
16#1018
16#1019
1
2
DWORD
DWORD
03 B0 00 00
02 00 07 69
L_9400_HL_S
1002
1002
16#1020
16#1021
1
2
DWORD
DWORD
3B 00 00 00
3D 9D 0738
L_9400_HL_S
1003
1003
16#1022
16#1023
1
2
DWORD
DWORD
3B 00 00 00
3D 9D 07 38
Column
Description
Notation
Name
Device name of the EtherCAT slave (optional)
STRING
Address
Address of the EtherCAT slave (required)
–
If no additional identification features are required for a slave, the entire line must be omitted.
 
–
If more than one identification feature is to be requested for a slave, a completely new line has to be created.
 
INT
(decimal)
Index
Index of the CoE object to be requested. (required)
INT
(hexadecimal with prefix 16#)
Subindex
Subindex of the CoE object to be requested. (required)
SINT
(decimal)
Type
Type of the CoE object to be requested. (required)
–
Only BYTE, WORD and DWORD are supported.
 
IEC basic types
(String)
Data
Data that must be contained in the specified CoE object. (required)
–
The number of bytes must comply with the type.
 
Octet stream
(hexadecimal with spaces)
Example:
–
0x00001234
 
–
4660
 
–
34 12 00 00
 
Comment
Comment field for the user. (optional)
STRING
 
Dependencies between configuration files and services
Depending on the selected service, information from the machine configuration file "mmc-0-conf.csv" and the file for further identification features of the slaves "mmc-0-ident.csv" is required. If the files are not available or if there is a "Parsing Error", one of the following error messages results when a service is activated: "CONFIG_FILE_ERROR" or "IDENT_FILE_ERROR".