Basic setting
In the following, the steps required for configuring the torque control are described.
1.
Select the SLVC motor control type.
2.
Carry out motor adjustment.
Configuring the motor control
Set the operating mode "MS: Torque mode [-1]" in 0x6060 (P301.00).
Configuring the motor control Set the operating mode "MS: Torque mode [-1]" in 0x6060 (P301.00).
3.
Select the standard setpoint source for the torque control in 0x2860:003 (P201.03). .
4.
Set the rated motor torque in 0x6076 (P325.00).
5.
Set the torque limits.
Torque limits
Torque limits 6.
Set the speed limitation.
Speed limitation
Speed limitation 7.
Configure additional standard setpoint source.
Configure setpoint sources
Configure setpoint sources 8.
Optional: setting of the torque setpoint ramp time 0x2948:002 (P336.02).
The following signal flow shows the internal setpoint logics:
The torque control with frequency limitation is now active and the inverter responds to the torque setpoint given by the selected setpoint source.