Safety instructions
Product information
Commissioning
Basic setting
Start, stop and rotating direction commands
Configuring the frequency control
Configuring the torque control
Basic setting
Configure setpoint sources
Process input data (CiA 402 objects)
Process output data (CiA 402 objects)
Setpoint diagnostics
Configuring the feedback system
Configuring the motor control
I/O extensions and control connections
Configuring the network
Device functions
Additional functions
Using accessories
Diagnostics and fault elimination
Technical data
Environmental notes and recycling
Appendix
i510 protec
i550 cabinet
i550/i650 motec
i550 protec
i750 cabinet
i950 cabinet
FAST Application Software
Process input data (CiA 402 objects)
These objects can be used for the CiA 402 "MS: Torque mode" operating mode. The CiA 402 operating mode "Profile Torque mode" is not supported.
Parameter
Address
Name / setting range / [default setting]
Information
0x6060
(P301.00)
CiA: Operation mode
(Operation mode)
–
Setting can only be changed if the inverter is disabled.
CiA: Operation mode
-2
MS: Velocity mode
Vendor specific velocity mode
Configuring the frequency control
-1
MS: Torque mode
Vendor specific torque mode
–
Only possible in motor control type
0x2C00 (P300.00)
= "Sensorless vector control (SLVC) [4]".
Configuring the torque control
0
No selection
No selection
2
CiA: Velocity mode (vl)
CiA: Velocity mode
CiA 402 device profile
0x6071
Set torque
-3276.8 ... [
0.0
] ... 3276.7 %
Setting of the setpoint torque for the torque operating modes.
–
100 % = Rated motor torque
0x6076 (P325.00)
The inverter does not support the CiA 402 torque mode.