Mains failure control

In case of power failure, this function can decelerate the motor and use its rotational energy to maintain the DC-bus voltage for a certain period of time. This makes it possible to continue to let the drive run during a short-term failure of the mains voltage. After mains recovery, the operating status that was active before the failure is adopted again.
 
Details
A failure of the mains voltage causes a continuous DC-bus voltage drop. If the mains failure control is enabled in 0x2D66:001 (P721.01), it will get active if the DC-bus voltage falls below the activation threshold set in 0x2D66:002 (P721.02).
As soon as the mains failure control is active, the motor is decelerated. Now the rotational energy of the motor is used to maintain the DC-bus voltage above the error threshold for undervoltage until the motor is decelerated to standstill in a controlled way. This process is controlled by the DC-bus voltage controller.
①
Current DC-bus voltage
②
Frequency setpoint (internal input signal)
③
Frequency setpoint (internal output signal for motor control)
The activation and commissioning of the mains failure control are described in detail in the following subchapters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D66:001
(P721.01)
Mains failure control: Enable function
(Mains fail. ctrl: Enable function)
–
From version 02.00
 
Enable mains failure control.
0
Disabled
Operation without mains failure control.
1
Enabled
Operation with mains failure control.
0x2D66:002
(P721.02)
Mains failure control: DC-bus activation level
(Mains fail. ctrl: DC-bus act.level)
60 ... [0]* ... 90 %
* Default setting dependent on the model.
–
From version 02.00
 
Threshold below which the mains failure control is activated if it is enabled (0x2D66:001 (P721.01) = 1).
–
100 % = nominal DC-bus voltage
 
Recommended setting:
–
In general: 5 ... 10 % above the error threshold for undervoltage (display in 0x2540:003 (P208.03)).
 
–
230-V devices: 72 %
 
–
400/480-V devices: 82 %
 
0x2D66:003
(P721.03)
Mains failure control: Gain V-controller
(Mains fail. ctrl: Gain V-ctrl)
0.00001 ... [0.01000] ... 0.50000 Hz/V
–
From version 02.00
 
Proportional gain of the DC-bus voltage controller.
0x2D66:004
(P721.04)
Mains failure control: Reset time V-controller
(Mains fail. ctrl: Res. time V-ctrl)
5 ... [20] ... 2000 ms
–
From version 02.00
 
Reset time of the DC-bus voltage controller.
0x2D66:005
(P721.05)
Mains failure control: DC voltage setpoint
(Mains fail. ctrl: DC voltage setp.)
80 ... [100] ... 110 %
–
From version 02.00
 
Voltage setpoint onto which the DC-bus voltage is to maintained.
–
100 % = nominal DC-bus voltage
 
0x2D66:006
(P721.06)
Mains failure control: Setpoint ramp
(Mains fail. ctrl: Setp. ramp)
1 ... [20] ... 16000 ms
–
From version 02.00
 
Acceleration time for the voltage setpoint set in 0x2D66:005 (P721.05).
–
The set acceleration time refers to the acceleration from 0 to 100 % of the nominal DC-bus voltage.
 
0x2D66:007
(P721.07)
Mains failure control: Clear time
(Mains fail. ctrl: Clear time)
1 ... [20] ... 60000 ms
–
From version 02.00
 
After the DC-bus voltage has exceeded the activation threshold 0x2D66:002 (P721.02) (+hysteresis) again, the time set here must be elapsed before the mains failure control is deactivated again if the restart protection is not activated (default setting).
0x2D66:008
(P721.08)
Mains failure control: Restart threshold
(Mains fail. ctrl: Restart level)
0.0 ... [0.0] ... 599.0 Hz
–
From version 02.00
 
Threshold for restart protection. Below the threshold set here no restart takes place after mains recovery.
0x2D66:009
(P721.09)
Mains failure control: Status mains failure control
(Mains fail. ctrl: RERT:Status)
–
Read only
 
–
From version 02.00
 
Bit coded display of the mains failure control status.
Bit 0
Control active
1 = mains failure control active.
–
The DC-bus voltage has fallen below the activation threshold 0x2D66:002 (P721.02).
 
–
The bit is reset to 0 after the DC-bus voltage has exceeded the activation threshold (+hysteresis) again and the clear time set in 0x2D66:007 (P721.07) has elapsed.
 
Bit 1
I-Reset active
1 = I component of the speed controller of the motor control is reset.
–
Bit is set to 1 if bit 0 is set to 1 (mains failure control active).
 
–
Bit is reset to 0 if the frequency setpoint falls below 0.1 Hz.