Restart protection

The integrated restart protection prevents a restart in the lower frequency range if the mains voltage was only interrupted briefly (mains recovery before the motor stands still).
–
In the default setting 0x2D66:008 (P721.08) = 0 Hz, the restart protection is deactivated.
 
–
In order to activate the restart protection, set the restart threshold in [Hz] in 0x2D66:008 (P721.08) below which no automatic start shall take place after mains recovery.
 
–
If, in case of mains recovery, the output frequency is below the restart threshold, the restart protection gets active:
 
–
If the current DC-bus voltage is lower than the voltage setpoint 0x2D66:005 (P721.05), the motor is continued to be decelerated (until frequency 0 Hz).
 
–
If the current DC-bus voltage is higher than the voltage setpoint 0x2D66:005 (P721.05), the motor is accelerated in a controlled way until the output frequency exceeds the restart threshold.
 
 
–
If, in case of mains recovery, the output frequency is above the restart threshold, the motor is accelerated again to the frequency setpoint. Fast mains recovery 
 
Diagnostic parameters:
–
An active restart protection is displayed via the status bit 0 in 0x2D66:009 (P721.09) if the mains failure control is not active.
 
 
Terminating the active restart protection
If, after mains recovery, the restart protection is active, it can be terminated by the following actions:
–
Error reset via the trigger set in 0x2631:004 (P400.04).
 
–
Short-time inverter disable via the trigger set in 0x2631:001 (P400.01).
 
–
Restart via the trigger set in 0x2631:002 (P400.02).