Parameter data transfer

Service data objects (SDOs) make it possible to read and write all parameters of the inverter via CANopen.
 
Details
–
Two independent SDO channels are provided at the same time. SDO channel 1 is always active. SDO channel 2 can be activated via 0x2301:005 (P510.05).
 
–
An SDO is always transmitted with confirmation, i. e. the reception of an SDO frame is acknowledged by the receiver.
 
–
The identifiers for SDO1 and SDO2 are generated from the basic identifier (in compliance with the "Predefined Connection Set") and the node address set:
 
Object
Direction
Identifier
to the device
from the device
SDO1
l
Basic identifier 0x600 + node address
l
Basic identifier 0x580 + node address
SDO2
l
Basic identifier 0x640 + node address
l
Basic identifier 0x5C0 + node address
 
Structure of the SDO frame user data
The user data are shown in Motorola format:
1st byte
2nd byte
3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
See table below.
LOW byte
HIGH byte
LOW word
HIGH word
Address of the parameter to be read or written.
LOW byte
HIGH byte
LOW byte
HIGH byte
The following commands can be transmitted or received for writing and reading the parameters:
Command
1st byte
Data length
Info
hex
dec
Write request
0x23
35
4 bytes
Writing of a parameter to the inverter.
0x2B
43
2 bytes
0x2F
47
1 byte
0x21
33
Block
Write response
0x60
96
4 bytes
Inverter acknowledges a write request.
Read request
0x40
64
4 bytes
Reading of a parameter from the inverter.
Read response
0x43
67
4 bytes
Inverter response to a read request with the
current parameter value.
0x4B
75
2 bytes
0x4F
79
1 byte
0x41
65
Block
Error response
0x80
128
4 bytes
Inverter response to the incorrect execution of
the read/write request.
More precisely, the command byte comprises the following information:
Command
1st byte
Command specifier (cs)
Toggle (t)
Length*
e
s
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Write request
0
0
1
0
0/1
0/1
1
1
Write response
0
1
1
0
0
0
0
0
Read request
0
1
0
0
0
0
0
0
Read response
0
1
0
0
0/1
0/1
1
1
Error response
1
0
0
0
0
0
0
0
*Bit coding of the length: 00 = 4 bytes, 01 = 3 bytes, 10 = 2 bytes, 11 = 1 byte
e: expedited (shortened block service)
s: segmented (normal block service)
More commands are defined in the DS301 V4.02 CANopen specification (e. g. segmented
transfer).
 
Up to 4 bytes are available for parameter value entries. Depending on the data format, they are assigned as follows:
5th byte
6th byte
7th byte
8th byte
Parameter value (1 byte)
0x00
0x00
0x00
Parameter value (2 bytes)
0x00
0x00
LOW byte
HIGH byte
Parameter value (4 bytes)
LOW word
HIGH word
LOW byte
HIGH byte
LOW byte
HIGH byte
 
The parameter attribute list in the annex also specifies a so-called “scaling factor”. The scaling factor is relevant to the transmission of parameter values which are represented with one or several decimal positions in the parameter list. If the scaling factor is > 1, the value must be multiplied with the scaling factor specified before the transmission, so that the value can be transferred completely (as an integer value). On the SDO client side, the integer value must then be divided by the scaling factor again, in order to receive the original value with decimal positions.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x1200:000
SDO1 server parameter: Highest sub-index supported
–
Read only
 
0x1200:001
SDO1 server parameter: COB-ID client > server (rx)
–
Read only
 
Display of the receive identifier for SDO server channel 1 (basic SDO channel).
–
According to DS301 V4.02, the basic SDO channel can neither be changed nor deactivated.
 
0x1200:002
SDO1 server parameter: COB-ID server > client (tx)
–
Read only
 
Display of the transmit identifier for SDO server channel 1 (basic SDO channel).
–
According to DS301 V4.02, the basic SDO channel can neither be changed nor deactivated.
 
0x1201:000
SDO2 server parameter: Highest sub-index supported
–
Read only
 
0x1201:001
SDO2 server parameter: COB-ID client > server (rx)
0x00000000 ... [0x80000640] ... 0xFFFFFFFF
Specification of the receive identifier for SDO server channel 2.
–
If SDO server channel 2 is activated via 0x2301:005 (P510.05), this parameter is set to the value "node address + 0x640". This default setting can be changed.
 
0x1201:002
SDO2 server parameter: COB-ID server > client (tx)
0x00000000 ... [0x800005C0] ... 0xFFFFFFFF
Specification of the transmit identifier for SDO server channel 2.
–
If SDO server channel 2 is activated via 0x2301:005 (P510.05), this parameter is set to the value "node address + 0x5C0". This default setting can be changed.
 
0x1201:003
SDO2 server parameter: Node-ID of the SDO client
1 ... [0] ... 127
Specification of the node address for the SDO client.
0x2301:005
(P510.05)
CANopen settings: Activate SDO2 channel
(CANopen sett.: SDO2 channel)
1 = activate SDO server channel 2.
0
Not active
1
Active
0x2301:007
(P510.07)
CANopen settings: COB-ID Configuration - SDO2
(CANopen sett.: COB-IDConfigSDO2)
1 = COB-ID configuration -SDO 2 freely configurable.
0
Base + node-ID
1
Freely configurable