Predefined control and status words

For establishing a simple network connection, the inverter provides predefined control and status words for the device profile CiA 402, the AC drive profile as well as in the LECOM format.
 
Details
Process data are exchanged via cyclic data exchange between the network master and the inverter.
For the cyclic data exchange, the inverter is provided with 24 network registers.
–
12 network registers are provided as input registers for data words from the network master to the inverter.
 
–
12 network registers are provided as output registers for data words from the inverter to the network master.
 
–
Each network register is provided with a corresponding code that defines which parameters (or other data codes) are mapped to the network register.
 
–
The input and output registers are divided into three blocks (A, B, C) in each case, featuring 4 successive data words, respectively:
 
Network register
Input register
Output register
Network IN A0
Network IN A1
Network IN A2
Network IN A3
Network OUT A0
Network OUT A1
Network OUT A2
Network OUT A3
Network IN B0
Network IN B1
Network IN B2
Network IN B3
Network OUT B0
Network OUT B1
Network OUT B2
Network OUT B3
Network IN C0
Network IN C1
Network IN C2
Network IN C3
Network OUT C0
Network OUT C1
Network OUT C2
Network OUT C3
The terms "input" and "output" refer to the point of view of the inverter:
–
Input data are transmitted by the network master and received by the inverter.
 
–
Output data are transmitted by the inverter and received by the network master.
 
The assignment of the network registers and the number of data words that can be transmitted cyclically varies according to the network/communication protocol. Detailed information can be found in the documentation for the respective communication protocol.
Data mapping cannot be applied to all parameters. The mappable parameters are indicated accordingly in the "Parameter attribute list". Parameter attribute list 
 
 
The following table lists the predefined control and status words. These can be mapped to network registers for the cyclic exchange of data:
Name
Parameter
Associated mapping entry *
Further information
CiA control word
0x60400010
CiA status word
0x60410010
AC Drive control word
0x400B0110
AC Drive status word
0x400C0110
LECOM control word
0x400B0210
LECOM status word
0x400C0210
* A mapping entry consists of index, subindex and data length in bits of the parameter to be mapped.
There are also additional mappable data words to individually control the inverter:
General information about the process of data mapping can be found in the chapter of the same name for the corresponding network.