Information on the network

The following parameters serve to diagnose the communication activities between the inverter and the Modbus network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2322:001
(P511.01)
Active Modbus settings: Active node ID
(Modbus diag.: Active node ID)
–
Read only
 
Display of the active node address.
0x2322:002
(P511.02)
Active Modbus settings: Active baud rate
(Modbus diag.: Active baud rate)
–
Read only
 
Display of the active baud rate.
0
Automatic
Setting of the baud rate.
–
A change in the baud rate only becomes effective after a restart of Modbus communication.
 
–
If the automatic baud rate detection function is activated, the first 5 ... 10 messages are lost after switch-on.
 
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
57600 bps
7
115200 bps
0x2322:003
(P511.03)
Active Modbus settings: Data format
(Modbus diag.: Data format)
–
Read only
 
Display of the active data format.
0
Automatic
Automatic data format detection.
–
With this setting, the first 5 ... 10 messages are lost after switch-on.
 
1
8, E, 1
8 data bits, even parity, 1 stop bit
2
8, O, 1
8 data bits, odd parity, 1 stop bit
3
8, N, 2
8 data bits, no parity bit, 2 stop bits
4
8, N, 1
8 data bits, no parity bit, 1 stop bit
0x232A:001
(P580.01)
Modbus statistics: Messages received
(Modbus statistic: Mess. received)
–
Read only
 
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
 
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:002
(P580.02)
Modbus statistics: Valid messages received
(Modbus statistic: Val. mess. rec.)
–
Read only
 
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:003
(P580.03)
Modbus statistics: Messages with exceptions
(Modbus statistic: Mess. w. exc.)
–
Read only
 
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:004
(P580.04)
Modbus statistics: Messages with errors
(Modbus statistic: Mess. w. errors)
–
Read only
 
Display of the number of messages received with a faulty data integrity (parity, CRC).
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:005
(P580.05)
Modbus statistics: Messages sent
(Modbus statistic: Messages sent)
–
Read only
 
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232E:001
(P583.01)
Modbus diagnostics of last Rx data: Offset
(Rx data diagn.: Rx data offset)
0 ... [0] ... 240
For purposes of diagnostics, the last message received (max. 16 bytes) is shown in 0x232E:002 (P583.02)...0x232E:017 (P583.17). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232E:002
(P583.02)
Modbus diagnostics of last Rx data: Data byte 0
(Rx data diagn.: Last RxD byte0)
–
Read only
 
Display of the message received last.
0x232E:003
(P583.03)
Modbus diagnostics of last Rx data: Data byte 1
(Rx data diagn.: Last RxD byte1)
–
Read only
 
0x232E:004
(P583.04)
Modbus diagnostics of last Rx data: Data byte 2
(Rx data diagn.: Last RxD byte2)
–
Read only
 
0x232E:005
(P583.05)
Modbus diagnostics of last Rx data: Data byte 3
(Rx data diagn.: Last RxD byte3)
–
Read only
 
0x232E:006
(P583.06)
Modbus diagnostics of last Rx data: Data byte 4
(Rx data diagn.: Last RxD byte4)
–
Read only
 
0x232E:007
(P583.07)
Modbus diagnostics of last Rx data: Data byte 5
(Rx data diagn.: Letzt RxD-Byte5)
–
Read only
 
0x232E:008
(P583.08)
Modbus diagnostics of last Rx data: Data byte 6
(Rx data diagn.: Last RxD byte6)
–
Read only
 
0x232E:009
(P583.09)
Modbus diagnostics of last Rx data: Data byte 7
(Rx data diagn.: Last RxD byte7)
–
Read only
 
0x232E:010
(P583.10)
Modbus diagnostics of last Rx data: Data byte 8
(Rx data diagn.: Last RxD byte8)
–
Read only
 
0x232E:011
(P583.11)
Modbus diagnostics of last Rx data: Data byte 9
(Rx data diagn.: Last RxD byte9)
–
Read only
 
0x232E:012
(P583.12)
Modbus diagnostics of last Rx data: Data byte 10
(Rx data diagn.: Last RxD byte10)
–
Read only
 
0x232E:013
(P583.13)
Modbus diagnostics of last Rx data: Data byte 11
(Rx data diagn.: Last RxD byte11)
–
Read only
 
0x232E:014
(P583.14)
Modbus diagnostics of last Rx data: Data byte 12
(Rx data diagn.: Last RxD byte12)
–
Read only
 
0x232E:015
(P583.15)
Modbus diagnostics of last Rx data: Data byte 13
(Rx data diagn.: Last RxD byte13)
–
Read only
 
0x232E:016
(P583.16)
Modbus diagnostics of last Rx data: Data byte 14
(Rx data diagn.: Last RxD byte14)
–
Read only
 
0x232E:017
(P583.17)
Modbus diagnostics of last Rx data: Data byte 15
(Rx data diagn.: Last RxD byte15)
–
Read only
 
0x232F:001
(P585.01)
Modbus diagnostics of last Tx data: Offset
(Tx data diagn.: Tx data offset)
0 ... [0] ... 240
For purposes of diagnostics, the last message sent (max. 16 bytes) is shown in 0x232F:002 (P585.02)...0x232F:017 (P585.17). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232F:002
(P585.02)
Modbus diagnostics of last Tx data: Data byte 0
(Tx data diagn.: Last TxD byte0)
–
Read only
 
Display of the message sent last.
0x232F:003
(P585.03)
Modbus diagnostics of last Tx data: Data byte 1
(Tx data diagn.: Last TxD Byte1)
–
Read only
 
0x232F:004
(P585.04)
Modbus diagnostics of last Tx data: Data byte 2
(Tx data diagn.: Last TxD byte2)
–
Read only
 
0x232F:005
(P585.05)
Modbus diagnostics of last Tx data: Data byte 3
(Tx data diagn.: Last TxD byte3)
–
Read only
 
0x232F:006
(P585.06)
Modbus diagnostics of last Tx data: Data byte 4
(Tx data diagn.: Last TxD byte4)
–
Read only
 
0x232F:007
(P585.07)
Modbus diagnostics of last Tx data: Data byte 5
(Tx data diagn.: Last TxD byte5)
–
Read only
 
0x232F:008
(P585.08)
Modbus diagnostics of last Tx data: Data byte 6
(Tx data diagn.: Last TxD byte6)
–
Read only
 
0x232F:009
(P585.09)
Modbus diagnostics of last Tx data: Data byte 7
(Tx data diagn.: Last TxD byte7)
–
Read only
 
0x232F:010
(P585.10)
Modbus diagnostics of last Tx data: Data byte 8
(Tx data diagn.: Last TxD byte8)
–
Read only
 
0x232F:011
(P585.11)
Modbus diagnostics of last Tx data: Data byte 9
(Tx data diagn.: Last TxD byte9)
–
Read only
 
0x232F:012
(P585.12)
Modbus diagnostics of last Tx data: Data byte 10
(Tx data diagn.: Last TxD byte10)
–
Read only
 
0x232F:013
(P585.13)
Modbus diagnostics of last Tx data: Data byte 11
(Tx data diagn.: Last TxD byte11)
–
Read only
 
0x232F:014
(P585.14)
Modbus diagnostics of last Tx data: Data byte 12
(Tx data diagn.: Last TxD byte12)
–
Read only
 
0x232F:015
(P585.15)
Modbus diagnostics of last Tx data: Data byte 13
(Tx data diagn.: Last TxD byte13)
–
Read only
 
0x232F:016
(P585.16)
Modbus diagnostics of last Tx data: Data byte 14
(Tx data diagn.: Last TxD byte14)
–
Read only
 
0x232F:017
(P585.17)
Modbus diagnostics of last Tx data: Data byte 15
(Tx data diagn.: Last TxD byte15)
–
Read only